Appendix C. Troubleshooting

Appendix C.1. Driver Error Messages

Multiple protocol drivers may exist on a FieldServer. Each driver may produce its own error messages and the
FieldServer itself may produce error messages.

All messages produced by this driver begin "Cheetah:"

Error Message

Action Required

Cheetah:#1

Unknown

simulation function.

Report these messages to FieldServer Technologies.

Cheetah:#2

Simulation

function unknown.
Cheetah:#3 Protocol Error
(Start),

Incoming

msg

ignored - Waiting for next
msg.

Warning messages only. An incoming message was discarded because the
identifiers which mark the beginning of a message could not be found. You
cannot take any action to correct this message. If it occurs often check wiring,
noise and installation.

Cheetah:#4 Protocol Error
(Stop),

Incoming

msg

ignored - Waiting for next
msg.
Cheetah:#5 Protocol Error
(Chksum), Incoming msg
ignored - Waiting for next
msg.
Cheetah:#6 Protocol Error
(Unknown), Incoming msg
ignored - Waiting for next
msg.

Report this error to FieldServer Technologies.

Cheetah:#7a Err. Zone=%d
Max=%d
Cheetah:#7b

MapDesc

Error. Zone value error.
(%d)
Cheetah:#7c FYI. Warning.
Zone=%d. Max zone is panel
type

dependent.

Read

Manual.

An invalid zone has been specified. The zone causing the problem is printed in
parenthesis.

4

The largest possible zone number is 255. Only Cybercat panels support this
number of zones. Legacy panels support up to zone 239. Very old panels that
can only send message #6 can only report information for 127 panels.
If you are connected to a Cybercat panel and you get the FYI message you can
ignore it. If you are connected to some other panel and you get either the Err or
FYI message then you will need to correct the CSV file.

Cheetah:#8 MapDesc Error.
Device value error. (%d)

An invalid device has been specified. The device causing the problem is printed
in parenthesis.

4

Cheetah:#9 MapDesc Error.
Loop value error. (%d)

An invalid loop has been specified. The loop causing the problem is printed in
parenthesis.

44

4

Modify the CSV file, download to the FieldServer and restart the FieldServer for the changes to take effect.