Appendix D. Reference

Appendix D.1. Driver Scope

This driver has implemented cheetah command #6.0. These messages are produced by a Cheetah device
controller and are consumed by this driver. The driver has no control on the frequency of the messages and thus
cannot guarantee fresh data. In addition the protocol has no method for acknowledging messages so that in the
event of this driver having to discard a corrupt message, the message producer does not know and will not re-
send.

Appendix D.2. Panel Firmware Versions

The driver supports older versions of panel firmware which transmit a shorter version of the Panel Status
command. This shorter version contains only panel data whereas the newer version contains panel, zone & device
data.

Appendix D.3. Storing Panel Data

Panel data is stored in consecutive locations as described in the map below. For additional explanations on the
meaning of each data element contact FIKE directly.

Array Location Data Category

Data stored at this location

0

Active Counter (0..65535)

Active events in normal state

1

Active events in Process state

2

Active events in Trouble state

3

Active events in Supervisory state

4

Active events in Drill state

5

Active events in ? state

6

Active events in ? state

7

Active events in ? state

8

Active events in Abort state

9

Active events in Pre-Alarm1 state

10

Active events in Pre-Alarm2 state

11

Active events in Alarm state

12

Active events in Pre-Discharge state

13

Active events in Release state

14

Active events in Zone Discharge state

15

Active events in Water Mist state

16

Board Status Indicators (0 or 1) Alarm silence active 1=yes

17

Supervisory Silence Active 1=yes

18

Trouble Silence Active 1=yes

19

AC Power on Main Board 1=ok

20

AC Power on Aux Board 1=ok

21

Walk test Condition 1=on

22

Ground Fault Condition 1=ok

23

Ack Condition 1=on

24

Date & Time

Month