Configuration and Installation

7

AXB-IRS4 IR/Serial Interface (4 Ports)

Using AXlink for data and power

Connect the Central Controller's AXlink connector to the AXlink/RS-232 connector, on the rear

panel of the AXB-IRS4, for data and 12 VDC power, as shown in FIG. 6.

Using AXlink for data and a 12 VDC power supply

Connect the Central Controller's AXlink connector to the AXlink/RS-232 connector, on the rear

panel of the AXB-IRS4, and the optional 12 VDC power supply, as shown in FIG. 7.

Use the 12 VDC power supply when the distance between the AMX system and AXB-IRS4

exceeds the limits described in the Wiring Guidelines at 125 mA table on page 6. Make sure to

connect only the GND wire on the AXlink/RS-232 connector when using a 12 VDC power supply.

Do not connect the PWR wire to the AXlink connector's PWR opening.

Using the AXlink-to-DB-9 connector cable for a PC system

The AXlink/RS-232 connector, on the back of the AXB-IRS4, can be connected to a PC system

using a DB-9 connector cable. Connector pins 2, 3, and 5 are used for data and ground. The

following table lists the DB-9 wiring pinouts.

FIG. 6 AXlink data and power wiring diagram

FIG. 7 AXlink and optional 12 VDC power supply wiring diagram

PWR (+)

GND (-)

PWR(+)

PWR

AXM/RX

AXM

AXP/TX

AXP

GND (-)

GND

12 VDC PWR connector

on AXB-IRS4

AXlink/RS232 connector

on AXB-IRS4

no connection

Axcess Control System

PWR(+)

AXM/RX

AXP/TX

GND (-)

PWR (+)

GND (-)

PWR

AXM

AXP

GND

12 VDC PWR connector

on AXB-IRS4

AXlink/RS232 connector

on AXB-IRS4

Axcess Control System

12 VDC power supply

To use a PC, set the internal jumpers for RS-232 communication mode and the
DEVICE DIP switch positions 1 - 8 off (down).

DB-9 Wiring Pinouts

Pin Signal Function

Pin Signal Function

1

N/A

Not used

6

N/A

Not used

2

RXD

Receive data

7

RTS

Request to send (not used)

3

TXD

Transmit data

8

CTS

Clear to send (not used)

4

DTR

Data terminal ready (not used)

9

N/A

Not used

5

GND

Signal ground