Allied Air Enterprises 4HP16LT User Manual

Page 12

Advertising
background image

START-UP

1. Rotate fan to check for frozen bearings or binding.

2. Inspect all factory and field-installed wiring for loose

connections.

3. After evacuation is complete, open liquid line and suction

line service valves to release refrigerant charge (contained

in outdoor unit) into system.

4. Replace the stem caps and secure finger tight, then

tighten an additional 1/6 of a turn.

5. Check voltage supply at the disconnect switch. The

voltage must be within the range listed on the unit nameplate.

If not, do not start equipment until the power company has

been consulted and the voltage condition corrected.

6. Set thermostat for cooling demand, turn on power to

indoor blower, and close the outdoor unit disconnect switch

to start the unit.

7. Recheck unit voltage with unit running. Power must be

within range shown on unit nameplate.

Refrigerant Charging

This system is charged with R410A refrigerant which

operates at much higher pressures than R-22. The liquid

line drier provided with the unit is approved for use with

R410A. Do not replace it with one designed for use with R-

22. This unit is NOT approved for use with coils which
use capillary tubes as a refrigerant metering device.

R410A refrigerant cylinders are rose colored.
Refrigerant should be added through the suction valve
in the liquid state.

Certain R410A cylinders are identified as being equipped
with a dip tube. These allow liquid refrigerant to be
drawn from the bottom of the cylinder without inverting
the cylinder. Do not turn this type of cylinder upside
down to draw refrigerant.

Units are factory charged with the amount of R410A

refrigerant indicated on the unit rating plate. This charge is

based on a matching indoor coil and outdoor coil with 15’

line set. For varying lengths of line set, refer to Table 4 for

refrigerant charge adjustment. A blank space is provided

on the unit rating plate to list the actual field charge.

If the system is void of refrigerant, clean the system using

the procedure described below.

1. Use dry nitrogen to pressurized the system and check

for leaks. Repair leaks, if possible.

2. Evacuate the system to remove as much of the moisture

as possible.

3. Use dry nitrogen to break the vacuum.

4. Evacuate the system again.

5. Weigh the appropriate amount of R410A refrigerant (listed

on unit nameplate) into the system.

6. Monitor the system to determine the amount of moisture

remaining in the oil. Use a test kit to verify that the moisture

content is withing the kit’s dry color range. It may be

necessary to replace the filter drier several times to achieve

the required dryness level. If system dryness is not
verified, the compressor will fail in the future.

The outdoor unit should be charged during warm weather.

However, applications arise in which charging must occur in

the colder months. The method of charging is determined

by the unit’s refrigerant metering device and the outdoor
ambient temperature.

Measure the liquid line temperature and the outdoor ambient

temperature as outlined below:

1. Connect the manifold gauge set to the service valve ports

as follows (See Figure 13 above):

If unit is equipped with a crankcase heater, it should be

energized 24 hours before unit start-up to prevent

compressor damage as a result of slugging.

CAUTION

Mineral oils are not compatible with R410A. If oil must

be added, it must be a polyolester oil.

IMPORTANT

Table 4

Liquid Line Set Diameter

Oz. Per 5 ft. adjust from 15

ft. line set*

3/8 in.

3 oz. Per 5 ft.

* If line length is greater than 15 ft., add this amount.

If line length is less than 15 ft., remove this amount.

Refrigerant Charge Adjustment

506468-01

Page 12

Issue 1004

Advertising