Allied Air Enterprises 4HP16LT User Manual

Page 9

Advertising
background image

removed during the first flush. After each system flush,
allow the recovery machine to pull a vacuum on the
system at the end of the procedure.

9. Close the valve on the inverted R22 cylinder and the

gauge set valves. Pump the remaining refrigeraant out of

the recovery machine and turn the machine off.

10. Use nitrogen to break the vacuum on the refrigerant

lines and indoor coil before removing the recovery machine,

gauges, and R22 refrigerant drum. Re-install pressure tap

valve cores into the 4HP16LT unit’s service valves.

11. Install a thermal expansion valve approved for use with

R410a refrigerant in the liquid line at the indoor coil.

Refrigerant Metering Device

4HP16LT units are designed for use with TXV systems only.

An R410a system will not operate properly with an R22

metering device.

Expansion valves equipped with Chatleff-type fittings are

available from the manufacturer. See Table 3 for proper

TXV for each unit.

To install an expansion valve (See Figure 9):

1. Separate the distributor assembly and remove the piston

orifice and used teflon seal. Insert nozzle end of the

expansion valve along with a new teflon seal into the

distributor and tighten to 20 - 30 ft. lbs. Use backup wrench

on all wrench flats. Overtightening will crush the teflon
seal and may cause a leak.

2. Attach liquid line portion of distributor assembly along

with new teflon seal to the inlet of the expansion valve.

Tighten to 20 - 30 ft. lbs. Use backup wrench on all wrench

flats. Overtightening will crush the teflon seal and may
cause a leak.

3. Connect the external equalizer line to the equalizer port

on the suction line and tighten to 8 ft.lbs.

506468-01

Page 9

Issue 1004

Table 3

TXV Data

MODEL

PART NUMBER

4HP16LT- 24

4HP16LT - 36

H4TXV01
H4TXV02

4HP16LT - 48, -60

H4TXV03

4. Strap the superheat sensing bulb to the suction header.

If installing an expansion valve on an indoor coil that

previously used a fixed orifice, be sure to remove the existing

fixed orifice. Failure to remove a fixed orifice when installing

an expansion valve to the indoor coil will result in improper

operation and damage to the system.

Manifold Gauge Set

Manifold guage sets used with systems charged with R410A

refrigerant must be capable of handling the higher system

operating pressures. The gauges should be rated for use

with pressures 1 - 800 on the high side and a low side of 30”

vacuum to 250 psi with dampened speed to 500 psi. Gauge

hoses must be rated for use at up to 800 psi of pressure

with a 4000 psi burst rating.

Liquid and Suction Line Service Valves

The liquid line and suction line service valves (See Figure

11) and service ports are used for leak teating, evacuation,

charging, and checking charge.

Each valve is equipped with a service port which has a

factory-installed Schrader valve. A service port cap protects

the Schrader valve from contamination and serves as the

primary leak seal.

To Access the Schrader Port:

1. Remove the service port cap with an adjustable wrench.

2. Connect gauge to the service port.

3. When testing is completed, replace service port cap.

Tighten finger tight, then an additional 1/6 turn.

Figure 9

Advertising