Low Battery Warning.
PowerChute interface

software provides auto-

matic, unattended shut-

down when approximately

two minutes (by default) of

battery operated run time

remains.

Brightly lit: Low battery

warning interval is about

two minutes.

Dimly lit: Low battery

warning interval is about

five minutes.

Off: Low battery

warning interval is about

eight minutes.

Possible interval settings:

2, 5, 8, 11, 14, 17, 20, 23

minutes.

The low battery warning

beeps are continuous when

two minutes of run time re-

main.
To change the warning inter-

val default setting, press the

voltage sensitivity button (use

a pointed object such as a pen

to do so), while pressing and

holding the

button (front

panel).

Synchronized Turn-on

Delay

0 seconds

60, 120, 180, 240, 300,

360, 420 seconds

The UPS will wait the speci-

fied time after the return of

utility power before turn-on

(to avoid branch circuit over-

load).

High Transfer Point

230V models:

253VAC
120V models:

127VAC
100V models:

108VAC

230V models:

257, 261, 265VAC
120V models:

130, 133, 136VAC
100V models:

110, 112, 114VAC

To avoid unnecessary battery

usage, set the high transfer

point higher if the utility volt-

age is chronically high and

the connected equipment is

known to work under this

condition.

Low Transfer Point

230V models:

208VAC
120V models:

106VAC
100V models:

92VAC

230V models:

196, 200, 204VAC
120V models:

97, 100, 103VAC
100V models:

86, 88, 90VAC

Set the low transfer point

lower if the utility voltage is

chronically low and the con-

nected equipment can tolerate

this condition.

Output Voltage

230V models:

230VAC

230V models:

220, 225, 240VAC

230V models ONLY: allows

the user to select the on bat-

tery output voltage.