UPS

OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTS

UPS input circuit breaker tripped.

Reduce the load on the UPS by unplugging equipment and resetting the

circuit breaker (on the back of UPS) by pressing the plunger in.

Very high, low, or distorted line

voltage. Inexpensive fuel powered

generators can distort the voltage.

Move the UPS to a different outlet on a different circuit. Test the input

voltage with the utility voltage display (see below). If acceptable to the

connected equipment, reduce the UPS sensitivity.

B

ATTERY

C

HARGE AND

B

ATTERY

L

OAD

LED

S FLASH SIMULTANEOUSLY

The internal temperature of the

UPS has exceeded the allowable

threshold for safe operation.

Check that the room temperature is within the specified limits for opera-

tion.
Check that the UPS is properly installed allowing for adequate ventila-

tion.
Allow the UPS to cool down. Restart the UPS. If the problem continues

contact APC at,

www.apc.com/support

.

D

IAGNOSTIC

U

TILITY

V

OLTAGE

F

EATURE

Utility Voltage

The UPS has a diagnostic feature that displays the utility voltage. Plug

the UPS into the normal utility power.

Press and hold the

button to view the utility voltage bar graph dis-

play. After a few seconds the five-LED, Battery Charge,

, display on

the right of the front panel shows the utility input voltage.
Refer to the figure at left for the voltage reading (values are not listed on

the UPS).
The display indicates the voltage is between the displayed value on the

list and the next higher value.
Three LEDs light, indicating utility voltage within the normal range.
If no LEDs are lit and the UPS is plugged into a working utility power

outlet, the line voltage is extremely low.
If all five LEDs are lit, the line voltage is extremely high and should be

checked by an electrician.

The UPS starts a self-test as part of this procedure. The self-test does not affect the voltage display.