Technical data – Apollo XP95 User Manual

Page 10

Advertising
background image

page

10

Humidity:
(No condensation or icing)
0% to 95% relative humidity

Wind Speed:
Unaffected by wind
Atmospheric Pressure:
Unaffected

Electro-magnetic
Compatibility:
See page 21 for full details

IP Rating:
23D

Approvals & Regulatory
Compliance:
See page 21 for full details

Vibration, Impact & Shock:
To EN54-7:2000

Dimensions: (diameter x height)
Detector: 100mm x 42mm
Detector in Base:
100mm x 50mm

Weights:
Detector: 105g
Detector in Base: 157g

Materials:
Detector Housing: White
polycarbonate V-0 rated to
UL 94
Terminals: Nickel plated
stainless steel

Fig.8

Schematic diagram - XP95 Optical Smoke Detector

technical data

TECHNICAL DATA

XP95 Optical Smoke Detector
Detector Part No 55000-600/
620/660
Base Part No 45681-210

Specifications are typical
and given at 23°C and 50%
relative humidity unless
otherwise stated.

Detector Type:
Point type smoke detector for
fire detection and fire alarm
systems for buildings

Detection Principles:
Photo-electric detection of
light scattered in a forward
direction by smoke particles

Chamber Configuration:
Horizontal optical bench
housing an infrared emitter
and sensor arranged radially
to detect scattered light

Sensor:
Silicon PIN photo-diode

Emitter:
GaAs Infra-red light emitting
diode

Sampling Frequency:
1 second

Sensitivity:
Nominal response threshold
value of 0.12 dB/m when
measured in accordance with
EN54-7:2000

Supply Wiring:
Two wire supply, polarity
insensitive

Terminal Functions:
L1&L2

supply in and out
connections (polarity
insensitive)

+R

remote indicator
positive connection
(internal 2.2k

resistance to supply
+ve)

-R

remote indicator
negative connection
(internal 2.2k

resistance to supply
- ve)

Supply Voltage:
17 to 28 Volts dc

Quiescent Current:
340µA average, 600µA peak

Power-up Surge Current:
1mA

Duration of Power-up Surge
Current:
0.3 seconds

Maximum Power-up Time:
4 seconds for communications
(measured from application of
power and protocol)
10 seconds to exceed 10 counts
35 seconds for stable clean
air value

Alarm Level Analogue Value:
55

Clean Air Analogue Value:
25±7 counts

Alarm Indicator:
Clear light emitting diode
(LED) emitting red light

Alarm LED Current:
4mA

Remote LED Current:
4mA at 5V (measured across
remote load)

Type Code:
(210 43) 101 00

Storage Temperature:
-30°C to +80°C

Operating Temperature:
-20°C to +60°C

Guaranteed Temperature
Range:
(No condensation or icing)
-20°C to +60°C

Fig.10

Typical Temperature Response - XP95 Optical Smoke Detector

Fig.9

Typical Response Characteristic - XP95 Optical Smoke Detector

0832