Technical data – Apollo XP95 User Manual

Page 16

Advertising
background image

page

16

TECHNICAL DATA

XP95 Manual Call Point

Specifications are typical
and given at 23°C and 50%
relative humidity unless
otherwise stated.

Call Point Type:
Deformable element

Weight:
151g

Call Point Principle:
Operation of a switch

Alarm Indicator:
Red Light Emitting Diode (LED)

Fault Indicator:
Amber/yellow light emitting
diode (LED)

Type Code:
(2 1 0 4 3)

1 1 1 1 1

Supply Wiring:
Two-wire supply, polarity
sensitive

Loop connections L1/L2:
Terminal block

technical data

Operating Voltage:
17V-28V dc

Communication Protocol:
5V-9V peak to peak

Quiescent Current:
100µA
Power-up Surge Current:
1mA

Maximum Power-up Time:
1 second

Alarm Current, LED
illuminated:
4mA

Normal Analogue Value:
16

Alarm State Value:
64

Electro-magnetic
Compatibility:
See page 21 for full details

Temperature Range:
Max. continuous operating:

+60°C

Min. continuous operating:

0°C

Min. operating:

-20°C

(no condensation/icing)
Storage:

-30°C to +80°C

Humidity:
(No condensation)
0 to 95% relative humidity

Compliance Standard:
EN54-11:2001
EN54-17:2005 (isolated
version)

IP Rating:
24

Dimensions:
89mm x 93mm x 26.5mm
(manual call point)
87mm x 87mm x32mm
(back box)

Materials:
Housing: Red self-coloured
Polycarbonate/ABS
Hinged cover and locking
tag are also available,

part

number: 26729-152

XP95 glasses are also
available,

part number:

26729-154 (pack of 5)

Advertising