14

technical data

+R

remote indicator
positive connection
(internal 2.2k

resistance to positive
remote indicator
negative connection)

-R

remote indicator
negative connection
(internal 2.2k

resistance to negative)

Operating voltage:
17-28V DC

Communications protocol:
Apollo Series 90/XP95 5-9V
peak to peak

Quiescent current:
500µA average 750µA peak

Power-up surge current:
1mA

Maximum power-up time:
10s

Alarm LED current:
3.5mA

Remote LED current:
4mA at 5V (measured across
remote load)

Clean air analogue value:
23 +4/-0

Alarm level analogue value:
55

Alarm indicator:
2 colourless Light Emitting
Diodes (LEDs); illuminated
red in alarm
Optional remote LED

Electro-magnetic compati-
bility:
See page 21 for full details

Temperature range:
Max. continuous operating:

+60°C

Min. continuous operating:

0°C

Min. operating (no
condensation/icing): -20°C
Storage

-30°C to +80°C

Humidity:
(No condensation)
0 to 95% relative humidity

Effect of temperature on
optical detector:
Less than 15% change in
sensitivity over rated range.
Slow changes in ambient
conditions will automatically
be compensated and will
not affect sensitivity

Effect of atmospheric
pressure on optical sensor:
None

Effect of wind on optical
sensor:
None

IP rating:
23D

Approvals & Regulatory
Compliance:
See page 21 for full details

Vibration, Impact and
Shock:
To prEN54-7

Dimensions:
100mm diameter
50mm height
58mm (height in base)

Weight:
Detector:

105g

Detector in base:

160g

Materials:
Housing: White
polycarbonate V-0 rated
to UL94
Terminals: Nickel plated
stainless steel

Smoke element only:

Chamber configuration:
Horizontal optical bench
housing infra-red emitter
and sensor, arranged
radially to detect forward
scattered light

Sensor:
Silicon PIN photo-diode

Emitter:
GaAlAs infra-red light
emitting diode

Sampling frequency:
1 per second

WARNING:

if the control panel incorporates a drift compensation algorithm,

this should be disabled when polling the XP95 Multisensor detector.

TECHNICAL DATA

XP95 Multisensor Detector
Detector Part No 55000-885
Base Part No 45681-210

Specifications are typical
and given at 23°C and 50%
relative humidity unless
otherwise stated.

Detector Type:
Point type smoke detector for
fire detection and fire alarm
systems for buildings

Detector principle:
Smoke: Photoelectric

detection of light

scattered by smoke
particles
Heat: Temperature-sensitive

resistance

Type code:
Bits

(2 1 0 4 3)
1 0 1 1 1

Supply wiring:
Two-wire supply, polarity in-
sensitive

Terminal functions:
L1&L2

supply in and out
connections (polarity
insensitive)