CRTE COUNTER TOP RETHERMAILZER

INSTALLATION

L20-259, rev. 7 (09/13)

4

1.5. ELECTRICAL

CONNECTIONS

It is advised that this power supply be plugged into a wall receptacle that is controlled by the
ventilation control. This will prevent the appliance from being operated without the ventilator on. The
power requirements for your appliance are listed below.



















































CAUTION

Connecting the appliance to the wrong power supply may damage the appliance and void
the warranty.

WARNING

This appliance must be connected to a power supply having the same voltage and phase as
specified on the data plate located on the inside of the appliance door.

WARNING

DO NOT attempt to connect the appliance to an electrical supply other then that indicated
on the data plate. Electrical connection should be performed by qualified personnel.

WARNING

The electrical connection used by this appliance must comply with local codes. If there are
no local codes that apply, refer to the National Electrical Code (NEC), ANSI/NFPA 70 for
installation in the US. In Canada, refer to CSA Standard C22.2 and local codes. In all other
cases, refer to local and national codes and regulations.

WARNING

The appliance must be grounded in accordance with local code; if there is no local code,
comply with the NEC and ANSI/NFPA No. 70 latest edition (for US and Canadian
installations). In all other cases, refer to local and national codes and regulations. To
comply with European requirements, European models are equipped with an equalization-
bonding clamp. An equalization bonding lead must be connected to this clamp to provide
sufficient protection against potential difference. This clamp, located on the rear of the
appliance is marked with the following universal symbol.

WARNING

A country approved all pole circuit breaker with a minimum open contact gap of 3mm must
be used for proper installation. (CE countries)

WARNING

This equipment must be installed so that the plug is accessible unless other means for
disconnection from the power supply (e.g. a circuit breaker) is provided.

WARNING

If this appliance is permanently connected to fixed wiring, it must be connected by means
of copper wires having a temperature rating of not less then 167°F (75°C).

WARNING

All copper wiring for this appliance must be made in accordance with the wiring diagram(s)
located on the appliance.

Voltage/Phase KW Amps
200VAC, single phase 5.5

28

208VAC, single phase

6

29

220VAC, single phase

5

23

230VAC, single phase 5.5

24

240VAC, single phase

6

25