Technical Data

26

Beijer Electronics, MAEN843A

Additional emergency stop switch specifications

Power supply

+24 V DC (voltage tolerance 19.2 - 30 V DC according to
EN 61131-2).
CE: The power supply must conform with the
requirements for SELV or PELV according to IEC 950 or
IEC 742.
UL: The power supply must conform with the
requirements for class II power supplies.

Key switch

3 positions - internal connection

Ambient temperature

0

° to +50 °C

Storage temperature

-20

° to +70 °C

Relative humidity

5 - 95% non-condensed

Vibration resistance
(operation)

10 Hz

≤ f < 57 Hz with 0.15 mm

9 Hz

≤ f < 150 Hz with 2 g

(IEC 60068-2-6)

Shock resistance
(operation)

25 g / 11 ms
(IEC 60068-2-27)

EMC tests on the
operator panel

EC Council Directive relating to machinery 98/37/EC and
its amendment 98/79/EC:
EN 418
EN 954-1
EN 60204-1
EC Council Directive relating to electromagnetic com-
patibility 89/336/EEC and its amendments 92/31/EEC
and 93/68/EEC:
EN 61131-2

UL

UL508, UL1740

Parameter

Emergency stop switch

Connection

Twin circuit - external connection

Rated voltage

24 V DC

Min. current

10 mA (each contact)

Max. current

1000 mA (each contact)

Utilization category

DC-13 (in accordance with IEC 60947-5-1)

Parameter

M70