Intended Applications

The temperature switches are specifically applied for monitoring and controlling of operations using
maximum or minimum temperatures. A micro switch triggers an electrical signal when minimum or
maximum temperatures are reached.

DANGER

The switch may only be used in the specified fields of application (see type label).

The temperature has to be within the specified ranges, the pressure values and the electrical
rating must not exceed the values specified.

Observe also the applicable national safety instructions for assembly, commissioning and
operation of the switch.

The switch is not designed to be used as the only safety relevant element in pressurized systems
according to DGR 97/23/EC.

2

Safety Instructions

The safety instructions are intended to protect the user from dangerous situations and/or material
damage.

In the operating instructions the seriousness of the potential risk is designated by the following
signal words:

DANGER

Refers to imminent danger to men.

Non-observance may result in fatal injuries.

WARNING

Refers to a recognizable danger.

Non-observance may result in fatal injuries, and destroy the equipment or plant parts.

CAUTION

Refers to a danger.

Non-observance may result in light injuries and material damage to the equipment and/or to the
plant.

Local mount temperature switches

Measuring Ranges

Max. temperature at sensor

Adjustment range

Order code

[°F]

[°F]

201

-100…

+250

-49…

+75.2

202

-100…

+250

15.8…

+140

203

-100…

+250

75.2…

+200

351

-100…

+401

100…+244.6

204

-100…

+200

-49…

+200

354

-100…

+401

100…+350.6

454

-0.4…

+500

150.8…+449.6

Reset values

Adjustment

range

Approximate hysteresis of different types of micro switches

Order code

[°F]

GH, H

J

M

S

adjustable

from

G*

201…354

-49…+350.6

1 – 2.8

2.2 - 4

1 - 4

6 - 20

5.0

454

150.8…+449.6

2.8 - 6

2.8 - 5

4 - 6.8

10 - 30

5.0

* can be reset

IMPORTANT

The values given are for use in liquids. For gaseous media hysteresis will be approx. double the values.