Barksdale L2H User Manual

Page 7

Advertising
background image

Contacts: color code and function

Contacts

C

= Common

= purple

NC

= Normally
Closed
Contact

= blue

NO

= Normally
Open Contact

= red

Contacts: color code and function

Lower contacts

Upper contacts

C

= Common

= purple

C

= brown

NC

= Normally
Closed
Contact

= blue

NC

= orange

NO

= Normally
Open Contact

= red

NO

= yellow

Fig. 8: Temperature switch type T1X-…/T1X-EX…

Fig. 9:Temperature switch type T2X-…/T2X-EX...

IMPORTANT

Adjustment of several set points is performed for each set point as specified above.

Due to the sluggishness of the capillary system switching delays may occur in case of rapid
temperature changes (>2 °C/Minute).

Wiring Code for all Types (Contact status at atm. pressure)

Power circuit

1

Power circuit

2

C = purple

C = brown

NC = blue

NC = orange

NO = red

NO = black

Circuit

1 = lower contact (low)

Circuit

2 = upper contact (high)

Fig. 5

Wiring Code

Use in Hazardous Locations

The weather-proof standard temperature switches must not be used for hazardous locations.

Special temperature switch types; T1X-EX, T2X-EX and L1X-EX for Ex d IIC T6 explosion-proof

applications with Certificate No. ISSeP 08 ATEX 024X.

These special models are suitable for gas and dust applications and approved for Ex II G D in

accordance with the ATEX 94/9/EC regulations.

These special switches with explosion-proof enclosure must be wired with Ex Certified conduit

connection, or cable gland. The switches may only be used in accordance with the instructions and

provisions of the declaration of conformity.

½“ NPT conduit
connection

46 (1.81)

10

2

(

4

.016)

16

0

(

6.

3)

75

(2.

95)

28.6 (1.13)

Ground screw
(internal)

Mounting holes
ø7.1 x 2

46

(

1.

81)

ш4.75
(0.11)

ш2.4
(0.09)

Terminal strip for
three connections

14.3
(0.56)

25.4 mm (1.0 inch) min.
required to remove the cover.

25.4 mm (1.0 inch) min.
required to remove the cover.

Terminal strip for
three connections

6.4
(0.25)

73 (

2.

8

7

)

161 (

6.

3

4

)

63.

5 (

2.

5)

11

3

(

4.

45)

ш4.75 (0.11)

ш2.4 (0.09)

ш9.6

(0.38)

*

**

* ¾“ NPT conduit

connection

** Ground screw

(internal)

136 (5.35)

Mounting holes
ø7.1 x 2

51
(2.008)

36.5 (1.44)

5

1

(2

.0

08)

Adjustment knob under cover

Adjustment knob under cover

NO

NC

C

NO

NC

C

1

2

7

10

Advertising
This manual is related to the following products: