OUTDOOR GRILLE

(OPTIONAL ACCESSORY)

An outside grille must be Installed to direct air flow for

proper unit operation and also protect the outdoor

coil. The grille must be installed before installing

the chassis. When replacing an old chassis with an

existing grille or using a specialized grille In a new

Installation, please check with after-sales engineer

of supplier to determine if the new chassis should

be used with the nonstandard specialized grille.

An improper outdoor grille can decrease cooling or

heating capacity,increase energy usage and shorten

compressor life and possibly void the warranty.

PACKAGED TERMINAL A/C

OWNER’S MaNual

Heat Controller

5

Preparation of the Wall

The sleeve should be installed during construction

and lintels should be used to support the block above

the wall sleeve. The sleeve can not support the load

of bricks/ blocks.

For existing construction, wall opening must be

created,the proper dimensions are necessary to

avoid use of fillers or additional framing .The sleeve is

modular in height and width (refer to Fig. 3 & Chart 2).

Height:

Fits 2 courses concrete block

Fits 6 courses standard brick

Fits 5 courses jumbo brick

Width: Fit approximately 3 stud spaces.

In order for condensate water to drain property inside

the unit, the sleeve must be installed properly:

• Level from right to left.

• A slight downward pitch from the indoor side to the

outdoor side as shown below Fig. 4).

• Fasten the wall sleeve (Fig. 5).

STAMPED ALUMINUM GRILLE

ARCHITECTURAL GRILLE

Fig. 5

Fig. 3

Fig. 4 Proper Sleeve Tilt

Minimum Finished

Opening Dimensions Approximate Sleeve Dimensions

Height

Width

Height

Width

Depth

16-1/4”

42-1/2”

16”

42”

13-3/4”

Note: Sleeves may vary be slightly manufacturer.

Ensure that the unit fits the sleeve before installation.

Chart 2