R208 Microstepping Driver Manual

8/31/2007

7. CONFIGURING AND CONTROLLING THE R208

Signal Control Specifications

Default Settings

Current

1.4 Amp

Step Resolution

8x microstep

Direction of rotation

Counterclockwise

Current Cutback
Switch

Enabled

Read step pulse from

Falling Edge (-)

Table 3: Default Settings
The R208 is set to these default

settings when Pins 2, 3, 4, and 5
are left open and untouched.

Step Resolution

SR1

(Black)

SR2

(Brown)

Full

Close

Close

Half

Close

Open

1/4

Open

Close

1/8

Open

Open

Table 4: Step Resolution Settings
SR1 (Pin 2) and SR2 (Pin 3) are used

to preset the step resolution by
selective contact closure to ground

(Pin 7).

WARNING: Do not change the Step Resolution on the fly, loss of step will

occur.

Enable/Disable

Enable

Open

Disable

Close

Table 5
Disable the Driver by closing the connection

between Pin 4 and Signal Ground.


Direction

Clockwise

Close

Counterclockwise

Open

Table 6

Change direction of rotation by closing the
connections between Pin 5 and the Signal

Ground.

Step Pulse Input Read Selection

The R208 RoHS version now has the option to change the way the R208 reads in the step
pulse train. By default, it understands one pulse when it reads the falling edge of the pulse.

To change this setting so that it reads one pulse when it sees a rising edge of the pulse,
simply turn power off, switch the dipswitch towards the “+” (positive) silkscreen marker,

then power back on.

Note: Old units read the pulse on the falling edge (-).