R325I Single Axis Controller/Driver Manual

02/13/2006

NOTE:

These recommendations will provide optimal protection against EMI and RFI. The

actual cable type, wire gauge, shield type and filtering devices used are dependent on the
customer’s application and system.

Driver Supply Cable AWG Table

1 Amp (Peak)

Length (Feet)

10

25

50*

75*

100*

Minimum

AWG

20 20 18 18 16

2 Amp (Peak)

Length (Feet)

10

25

50*

75*

100*

Minimum

AWG

20 18 16 14 14

3 Amp (Peak)

Length (Feet)

10

25

50*

75*

100*

Minimum

AWG

18 16 14 12 12

* Use the alternative methods illustrated in Examples B and C

when the cable length is ≥ 50 feet. Also, use the same current

rating when the alternate AC power is used

Driver Supply Cable Wire Size

NOTE: Always use Shielded/Twisted Pairs for the Driver DC Supply Cable, the AC Supply
Cable and the Driver to Motor Cable.