Figure 2: pl-8 underside, Table 2: underside features, Instead of “p – Kramer Electronics PL-8 User Manual

Page 7: And “p, Instead of “rs-485 t

Advertising
background image

KRAMER: SIMPLE CREATIVE TECHNOLOGY

Your PL-8 Low Voltage Relay Controller

4

Table 1: PL-8 Low Voltage Relay Controller Features

#

Feature

Function

1

REL Terminal Block (from 1 to 4) Connect to room items

1

2

. The PINOUT is: NO: Normally Open;

C: Common Voltage; NC: Normally Closed

REL Terminal Block (from 5 to 8) Connect to room items

1

. The PINOUT is: NO: Normally Open;

C: Common Voltage

3

RS-232 Terminal Block

Connects to the RS-232 port on a PC

4

K-NET™

2

PIN GND is for the Ground connection

Terminal Block

Connector

3

5

; PIN B (-) and PIN A

(+) are for RS-485, and PIN +12V is for powering the unit

LINK LED

Illuminates when a link is established

6

ON LED

Illuminates when receiving power

Figure 2 and Table 2 define the underside of the PL-8. On some units the

printing of the labels “RS-485 T

ERM

” (instead of “P

ROGRAM

”) and

“P

ROGRAM

” (instead of “RS-485 T

ERM

”) may be swapped around

erroneously. The correct labeling is defined in Figure 2 and Table 2.

Figure 2: PL-8 Underside

Table 2: Underside Features

#

Feature

Function

1

CONTROL DIP-switches

4

Set DIP 8 ON to use protocol 2000

Set DIP 8 0FF to use protocol 3000 over K-NET™

2

RS-485 TERM Switch

Switch for line termination of the unit

3

PROGRAM Switch

Switch to PROGRAM for firmware upgrade

1 Such as lighting, screen settings, blinds, and so on
2 K-NET is a proprietary Kramer protocol for interconnecting Kramer units
3 The ground connection is sometimes connected to the shield of the RS-485 cable (in most applications, it is not connected)
4 DIPs 1 to 7 are not used