M&G DuraVent DuraTech® 5-8 User Manual

Page 8

Advertising
background image

8

Support, refer to the Square ceiling installation

below. The Round Ceiling Support Box has

the option of a square or round Trim Collar

available (Fig 5). The bottom of the Round

Support Box must extend at least 3 inches

below the finished ceiling. Level the Support

Box and secure it to the framing using at least

three 8-penny nails per side (min. of 12 total).

Alternatively, you may use 1-1/2” #8 wood

screws (min. of 12 total), instead of nails.

Next, secure the Trim Collar (round or square)

to the framing members using the (4) 1” long,

round-head wood screws provided (Fig 6).

For installation into a cathedral ceiling, you

must use the Square Ceiling Support Box or

Reduced Clearance Support Box (or the CAS

Ceiling Support if installing the CAS system)

and the two-piece Trim. The bottom of the

square portion of the Support Box must be a

minimum of 2-inches lower (round portion is

an additional 3 inches lower) than the finished

ceiling at the lowest side of the penetration

(Fig 5 & 6). Level the Support Box and

secure it to the framing using at least three (3)

8-penny nails per side (minimum of 12 nails

total), or a minimum of (3) #8, 1-1/2” wood

screws. Adjust the overlapping “U-shaped”

Trim pieces so they cover the Support Box,

and secure them to the framing members

using the (6) 1-1/4” long, round head wood

screws provided (see Fig 6).

4. Frame Openings: Frame openings in

each ceiling or floor above the Support Box

(Fig 7). These openings are to hold the

Firestop Radiation Shield and Attic Insulation

Shield. Locate each opening by dropping a

plumb bob to the four corners of the opening

below. Maintain the framing dimensions as

specified in Table 2.

Warning: other than the framing for the

Reduced Clearance Support Box, any

combustible materials around the chimney

must still meet the minimum 2” clearance

requirement. If Elbows must be used to

avoid an obstruction, refer to the Offset Elbow

Installation section.

5. Cut Roof Opening: Cut an opening in the

roof directly above the opening below, and

at least 4 inches larger than the chimney’s

outside diameter to provide at least a

2-inch clearance all around the chimney.

The chimney must be centered within this

Figure 6

Figure 7

MIN OF 2

INCHES

BELOW

FINISHED

CEILING

WOOD SCREWS ARE

REQUIRED

WOOD SCREWS ARE

REQUIRED

ROUND CEILING

SUPPORT WITH TRIM

IN PLACE

SQUARE CEILING

SUPPORT BOX WITH

TRIM FRAME

IN PLACE

CAP

ADJUSTABLE

FLASHING

CHIMNEY

SECTION

ATTIC

INSULATION

SHIELD

STORM

COLLAR

FIRESTOP

RADIATION

SHIELD

CHIMNEY

SECTION

FRAMED

ENCLOSURE

2 INCH MIN

CLEARANCE

TO INSIDE OF

ENCLOSURE

MIN OF 3

INCHES BELOW

FINISHEDCEILING

18 INCH MIN FOR

SINGLE WALL

STOVEPIPE

Advertising