Warning – M&G DuraVent DuraTech® Canada User Manual

Page 4

Advertising
background image

4

GENERAL INSTALLATION NOTES

1

1. The chimney is intended for use with solid (6’’,7’’,8’’ dia. only) or

liquid and gaseous fuel burning appliances.(all diameters)

Allowable flue gas temperature:

Maximum continuous 540°C (1000°F)

Brief forced firing 760°C (1400°F)

Tested to 1150°C (2100°F) - 30 minutes

2. On wood or coal stove application and in area where the chimney

is completely enclosed, it is required to install Premium shields

(telescopic of flexible) around the chimney and a Radiation shield

connector at the ceiling level.

For venting of gas or oil burning appliances Premium shields are

not required even where the chimney is enclosed.

For factory-built wood burning fireplaces, Premium shields

are usually not required, please follow fireplace installation

instruction.

3. The maximum height of chimney supported by the various supports

are outlined on page 3.

4. The supports described in this booklet should only be used with

Duravent model DURATECH CANADA (DTC), 5", 6", 7", 8" and 10"

factory built chimneys.

5. Size the chimney in accordance with the appliance manufacturer's

instructions.

6. When a firestop (DTC-FS , DTC-ISI or DTC-RSCI) needs to be

installed, it is important to follow the opening dimensions for the

floor openings prescribed in this manual. This way, the holes left

by the folded positioning tab of the firestop will be blocked by the

ceiling.

7. A chimney servicing a fireplace or an incinerator shall not serve any

other appliance.

8. The chimney shall extend at least 3 ft above its point of contact

with the roof and at least 2 ft higher than any wall, roof or adjacent

building within 10 ft of it.

9. The maximum height of unguided chimney above the roof is 5 ft.

10. The clearance between single wall pipe and unprotected combustible

material must not be less than 18" (see national building code and

NFPA 211) except: The distance between the vertical stove pipe and

the ceiling may be less than 18" and will be established by the finish

support.

11. Portions of the chimney which may extend through accessible

spaces shall be enclosed in all cases to avoid personal contact

with the chimney and damage to the chimney. When doing so on

woodstove or coal application, a telescopic or flexible Premium

shield must be installed (see Figure 2). Except for installation in

single and two-story family dwellings, the enclosure must have a

fire resistance rating equal to or greater than that of the floor or

roof assemblies through which they pass.

12. Do not fill the 2" space around the chimney with insulation or any

other material. Insulation placed in this area could cause adjacent

combustibles to overheat.

13. Self tapping screws are not required, but may be used to reinforce

the connection and avoid accidental unlocking of chimney lengths.

2 ft

MIN.

10 ft

3 ft

MIN.

2" MIN.

ENCLOSURE

2" MIN.

7 1/2"

MIN.

BASE TEE

* 18"

MINIMUM

* 18"

MINIMUM

* THE DISTANCE CAN BE REDUCED IF A

LISTED STOVE PIPE IS USED.

Figure 2

WARNING

RADIATION

SHIELD

CONNECTOR

(DTC-RSCI)

STORM

COLLAR

(DTC-SC)

RADIATION

SHIELD

FIRESTOP

(DTC-FRSC)

SWIVEL

ADAPTOR

OPTIONAL

(DTC-SA)

PREMIUM SHIELD

(DTC-TRS or DTC-FLXS)

SUPPORT

(DTC-FSC

OR DTC-BS)

INSTALLATION NOTES

The clearance between the chimney and combustible

material must not be less than 2", except where

established by the support. Do not fill this area with

insulation.

Advertising