Zc kit – large pellet insert, Minimum floor protection – Travis ZC Kit – Large Pellet User Manual

Page 5

Advertising
background image

ZC Kit – Large Pellet Insert

(99200149)

Page 5 of 8

10/9/06

© Travis Industries, Inc.

Minimum Floor Protection

The insert must be placed on a non-combustible floor protector (cement board, sheet metal, etc.) a

minimum .018” thick (26 gauge). This floor protection must extend the full width and depth of the

enclosure and must protrude 6” in front of the door opening (18” from the enclosure opening) and the full

width of the surround panels (45” min. width).

HEARTH NOTE: If you wish to install a hearth greater than 1/2” thick, you will need to raise the insert and

enclosure height the equivalent amount. The leveling bolts may be used on the insert for adjustments.

45” Min.

(width of surround panels)

18” Min.

Floor Protection

Enclosure Height

(measure from top of

floor protection)

Floor Protection

Rear Vent Installations

Place the stove on top of the floor protection and measure the center of the

flue. This will determine the location of the wall thimble.

12”

Minimum