Caution, Placing a regulator in service – Howard SVR1 Regulator User Manual

Page 10

Advertising
background image

Document 2.4.114

SVR-1 Step Voltage Regulator

Copyright © 2012 Howard Industries, Inc.

Document No. 2.4.114

Revision: 03

Issued: March, 2012

10

PlACING A REGUlATOR IN SERVICE

PROCEDURE FOR PlACING IN SERVICE

After completing the installation procedure outlined in the

previous section, the regulator can be placed into service

using the following procedure.

1. Set HI-AMP™ limits, if necessary, using the rotary

switches located on either side of the position

indicator (Figure 9).

The HI-AMP™ feature allows the

SVR-1 regulator to be operated above rated load by

decreasing the range of operation in 1.25 percent

increments. Load current may be increased up to

160 percent of rated current (maximum of 668

Amps) when the regulator is operated at ± 5 percent

regulation. Percentages of current ratings for various

regulation ranges are as follows:

All that is necessary to adjust the range of regulation

anywhere from ±5 percent to ±10 percent is to

set the Hi-AMP™ switches to the desired range of

regulation is shown. The upper and lower limits

need not be the same. (Upper and lower limits of

operation can also be implemented with the digital

control unit.)

It is not necessary to remove the regulator from

service to make this adjustment; however, switches

should not be set while the motor is running.

2. Program the control unit as desired. Refer to the

manual supplied with the control unit.

3. Make absolutely certain that the regulator is in

neutral (0) position. Refer to both the position

indicator pointer and the neutral indicator on

the control panel. The position indicator must

point to “zero,” and the neutral indicator must be

continuously illuminated (The control panel can be

powered from a 120 Volt external source.)

4. Turn MAIN POWER and MOTOR CONTROL switches

to “OFF.”

5. Remove motor fuse.

6. Close the SL disconnect switch (Delta connections

only).

7. Sequentially close the source and then the load

disconnect switches.

8. Open the bypass switch.
9. Visually observe that bypass circuit is open.
10. Replace motor fuse.
11. Switch MAIN POWER switch to “INTERNAL.”

Voltage Range (%)

Current Rating (%)

±10

100

±8.75

110

±7.5

120

135

±5

160

±6.25

FIGURE 9

: One of two HI-AMP™ switches located on each

side of control position indicator

CAUTION

Operation of the regulator to extreme tap positions

can produce a line voltage that is above or below the

desired operating limit of the load.