Bryant T6-NHP User Manual

Page 29

Advertising
background image

27

Option 07 — Zoning
This selection should be set to On when the thermostat is to be used as part of a

zoning system. It is assumed that the zoning equipment will take care of time

guard and cycle timers. The minimum on time is still controlled by the

thermostat.
Default is OF (off).
Option 08 — Auxiliary Heat Lockout Temperature
This selection is available on heat pump systems with a valid outdoor

temperature sensor connected. Available settings are: Off, 5, 10, 15, 20, 25, 30,

35, 40, 45, 50, 55.
OF (off) − function is disabled. Auxiliary heat is allowed to operate whenever

sufficient demand for heat is available.
5 to 55

_F (−15 to 13_C) − Outdoor temperature above which the auxiliary heat

is not allowed to operate (unless MODE is set to Emergency Heat). If room

temperature falls below 45

_F (7_C), the auxiliary heat will be allowed to turn on

and will continue to run until demand is satisfied.
Default is OF (off).
Option 10 — Reversing Valve
This selection is only available on heat pump systems. “O” terminal can be

configured to be energized in either heating mode or in cooling mode, depending

on heat pump operation. “O” is used to describe a heat pump system that

energizes its reversing valve in cooling. “B” is used to describe a heat pump

system that energized its reversing valve in heating.
H — Reversing valve output (O/W2/B) is energized when HEAT mode is

selected.