Detect that defrost is in progress and energize the auxiliary heat to

provide homeowner comfort during the defrost cycle

S

Allow a defrost cycle to run to completion regardless of the system

demand

Three−Minute Minimum on Time
In normal operation, when a stage turns on, it will not turn off for a minimum of

3 minutes. If the setpoint is changed, this timer is canceled, allowing the

equipment to turn off immediately when the demand is removed.
Heat/Cool Setpoints (Desired Temperature)
A minimum difference of 1

_ and maximum of 6_ is enforced between heating

and cooling desired temperatures. This is done by allowing 1 setting to “push”

the other, to maintain this difference. This difference is adjustable via

Configuration Option 11.

Equipment On Indicators

When cooling equipment is on, a COOL ON icon is displayed. While cooling

equipment operation is delayed by the timeguard or cycle timer, COOL ON will

flash. The same is true for HEAT ON.
During second stage compressor operation a “2” will be displayed with the

HEAT ON or COOL ON icon. This is displayed when the thermostat is

configured as H2, A2, or h2.
When the W is energized in a heat pump, the auxiliary heat on icon will be

displayed.
Auto Changeover
When auto changeover mode is selected, a change from heat to cool (or vice

versa) will not occur until an opposite mode demand has existed for 20 minutes.

If setpoint is changed, 20−minute requirement is deleted.