3. INSTALLATION

(CONT’D)

3.9 I

NSTALLING

2 E

XTERIOR

H

OODS

Choose an appropriate location to install the exterior hoods:

There must be a minimum distance of 6 feet (1.8 m) between the hoods to avoid cross-contamination

There must be a minimum distance of 18 inches (457 mm) from the ground

Refer to figure below for connecting insulated ducts to the exterior hoods. An “Anti-gust intake hood” should be installed in regions where
a lot of snow is expected to fall.

VD0028

O

PTIONAL

DUCT LOCATION

E

XHAUST HOOD

I

NTAKE HOOD

18”

(457

MM

)

18” (457

MM

)

6” Ø

(152

MM

)

18”

(457

MM

)

6’

(1.8

M

)

6’

(1.8

M

)

- 16 -

WARNING

Make sure the intake hood is at least 6 feet (1.8 m) away (or more, as per applicable building codes or standards)
from sources of contamination such as:

• High efficiency furnace vent
• Any exhaust from a combustion source
• Gas meter exhaust, gas barbecue-grill
• Garbage bin

!

T

APE AND DUCT TIE