F. Mechanical Cooling Lockout

Determine the outdoor-air temperature at which the
mechanical cooling (compressors) will be disabled. Locate the
mechanical cooling lockout (MECH CLG LOCKOUT) poten-
tiometer. To disable this feature, turn the potentiometer
counterclockwise (CCW) to the OFF position. Otherwise, set
the value between 10 and 60 F. Mechanical cooling will not
operate when the outdoor air temperature is below this
value. See Fig. 17.

G. Dry Bulb Changeover Set Up

Determine the dry bulb changeover set point from Table 5.
The settings are A, B, C and D. Locate the ECON SP potenti-
ometer and set the dry bulb changeover set point. See

Fig. 17. When the OAT is above this set point, the damper is
limited to minimum position setting.

If a potentiometer fails, its setting will default to the values
in Table 6.

H. Ventilation Air (Minimum Position Set Up)

If ventilation air is not required, skip this section. If ventila-
tion air is required, perform the following:

1. The indoor fan must be on to set the ventilation air.

Either put the thermostat in the continuous fan mode
or jumper the R and G terminals at the rooftop unit
connection board.

Table 4 — EconoMi$er Switchover Control Strategy

*Must be selected manually.

Table 5 — Changeover Set Points

*Field-installed accessory.

Table 6 — Default Potentiometer Settings

ECONOMI$ER SWITCHOVER STRATEGY

SENSORS REQUIRED

Outdoor Air Temperature

Outdoor Air Enthalpy

Return Air Temperature

Return Air Enthalpy

Dry Bulb

X

Single Enthalpy

X

Differential Temperature

X

X

Differential Enthalpy*

X

X

SETTINGS

A

B

C

D

Dry Bulb (°F)

73

69

66

63

Single Enthalpy* (Btu/lb)

27

25

24

22

Differential Temperature*
(°F, Not Adjustable)

2

2

2

2

Differential Enthalpy*
(Btu/lb, Not Adjustable)

1

1

1

1

POTENTIOMETER

DEFAULT SETTING

CO

2

SP (PPM)

1,000

MECH CLG LOCKOUT

50 F

ECON SP

D

MIN POS (%)

20

LEGEND

*OAT sensor shipped with economizer option. OAH, RAT, RAH and CO

2

are field-installed accessories.

Fig. 24 — Typical EconoMi$er Sensor Wiring

CLG

Cooling

OAH —

Outdoor-Air Enthalpy Sensor

COM — Common

OAT

Outdoor-Air Temperature Sensor

DAT

Discharge Air Thermistor

POT

Potentiometer

DM

Damper Motor

RAH —

Return-Air Enthalpy Sensor

GND — Ground

RAT

Return-Air Temperature Sensor

LED

Light-Emitting Diode

REM —

Remote

Advertising