Bryant 558F User Manual

Page 21

Advertising
background image

21

Table 8 — Fan Performance — 558F180*

LEGEND

*Standard low-medium static drive range is 873 to 1021 rpm. Alternate high-static

drive range is 1025 to 1200. Other rpms require a field-supplied drive.

NOTES:

1. Maximum continuous bhp for the standard motor is 6.13. The maximum con-

tinuous watts is 5180. Do not adjust motor rpm such that motor maximum
bhp and/or watts is exceeded at the maximum operating cfm.

2. See page 23 for general fan performance notes.

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

753

1.53

1307

753

1.53

1307

784

1.64

1397

859

1.92

1635

928

2.20

1880

993

2.50

2133

4800

747

1.62

1384

747

1.62

1384

806

1.83

1563

878

2.12

1808

946

2.42

2060

1009

2.72

2319

5100

741

1.72

1465

752

1.76

1500

828

2.05

1745

898

2.34

1996

964

2.65

2255

1026

2.96

2521

5700

735

1.95

1659

805

2.22

1895

876

2.53

2156

942

2.84 2423

1004

3.16

2696

1064

3.49

2975

6000

759

2.18

1854

832

2.48

2118

901

2.80

2388

965

3.12 2663

1026

3.45

2943

1083

3.79

3228

6300

790

2.45

2088

860

2.77

2360

926

3.09

2638

988

3.43 2920

1048

3.76

3208

1104

4.11

3501

6600

821

2.74

2340

888

3.07

2621

952

3.41

2906

1013

3.75 3196

1070

4.10

3491

1125

4.45

3791

6900

852

3.06

2611

917

3.40

2900

979

3.75

3194

1038

4.10 3492

1094

4.45

3794

1147

4.81

4101

7200

883

3.40

2903

946

3.75

3200

1006

4.11

3501

1063

4.47 3807

1118

4.83

4117

1170

5.20

4431

7500

914

3.77

3215

975

4.13

3521

1033

4.49

3830

1089

4.86 4143

1142

5.23

4461

1193

5.61

4781

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.4

1.6

1.8

2.0

2.2

2.4

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

1055

2.81

2394

1114

3.12

2662

1170

3.45

2938

1224

3.78

3220

1276

4.12

3509

1326

4.46

3805

4800

1070

3.03

2585

1127

3.35

2859

1183

3.68

3139

1236

4.02

3427

1287

4.36

3721

1336

4.72

4020

5100

1086

3.28

2794

1142

3.60

3073

1196

3.94

3359

1248

4.28

3650

1299

4.63

3949

1347

4.99

4253

5700

1120

3.82

3260

1174

4.17

3551

1226

4.51

3848

1277

4.87

4151

1325

5.23

4458

1373

5.60

4772

6000

1139

4.13

3520

1192

4.48

3817

1243

4.83

4119

1292

5.19

4427

1340

5.56

4741

1387

5.93

5060

6300

1158

4.46

3799

1210

4.81

4102

1260

5.17

4410

1309

5.54

4724

1356

5.91

5043

6600

1178

4.80

4095

1229

5.17

4405

1278

5.54

4720

1326

5.91

5039

6900

1199

5.18

4412

1249

5.55

4728

1297

5.92 5050

7200

1221

5.57

4749

1270

5.95

5072

7500

1243

5.99

5107

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

2.6

2.8

3.0

3.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

4500

1375

4.82

4107

1421

5.18

4414

1467

5.55

4728

1511

5.92

5047

4800

1384

5.07

4326

1430

5.44

4638

1475

5.81

4955

5100

1395

5.35

4563

1440

5.72

4879

5700

1418

5.97

5091

6000

6300

6600

6900

7200

7500

Bhp

Brake Horsepower

Watts —

Input Watts to Motor

TB2

ROOFTOP UNIT

R
C

Y1

Y2

G

W1

W2

24 V

FROM
PERFECT
HUMIDITY
LLSV

R1

TSTAT WIRES

LCT

R
C

Y1

Y2

G

W1

W2

DEHUM

OC

R1

FIELD-SUPPLIED RELAY

HN61KK324

1

2

TB3

FROM
PERFECT
HUMIDITY
LLSV

Fig. 31 — Typical Perfect Humidity™ Dehumidification Package Thermidistat Wiring Schematic

LEGEND

LCT

Light Commercial Thermidistat

LLSV — Liquid Line Solenoid Valve
LPS

Low-Pressure Switch

TB

Terminal Block