Bryant 558F User Manual

Page 23

Advertising
background image

23

Table 11 — Fan Performance — 558F300*

LEGEND

*Standard low-medium static drive range is 1066 to 1283 rpm. Alternate high-

static drive range is 1332 to 1550. Other rpms require a field-supplied drive.

NOTES:

1. Maximum continuous bhp is 10.20 (208/230 v) or 11.80 (460 v) and the

maximum continuous watts are 9510 (208/230 v) or 11,000 (460 v). Do not
adjust motor rpm such that motor maximum bhp and/or watts is exceeded at
the maximum operating cfm.

2. See below for general fan performance notes.

GENERAL FAN PERFORMANCE NOTES

NOTES:

1. Values include losses for filters, unit casing, and wet coils. See Table 12

below for accessory/factory-installed option static pressure information.

2. Extensive motor and electrical testing on these units ensures that the full

range of the motor can be utilized with confidence. Using your fan motors up
to the wattage ratings shown will not result in nuisance tripping or premature

motor failure. Unit warranty will not be affected. See Table 14 for Evaporator-
Fan Motor Performance on page 24 for additional information.

3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant

representative for details.

4. Interpolation is permissible. Do not extrapolate.

Table 12 — Accessory/FIOP Static Pressure (in. wg)* — 558F180-300

LEGEND

*The static pressure must be added to external static pressure. The

sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm and
watts.

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

1.2

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

845

3.26

2693

909

3.60

2979

969

3.96

3272

1028

4.32

3574

1083

4.70

3883

1137

5.08

4,200

7,500

896

3.82

3156

956

4.17

3450

1014

4.54

3752

1069

4.91

4060

1123

5.29

4375

1174

5.68

4,698

8,000

948

4.43

3667

1005

4.80

3969

1060

5.17

4278

1112

5.56

4593

1163

5.94

4915

1213

6.34

5,243

8,500

1001

5.11

4226

1054

5.49

4537

1106

5.87

4853

1156

6.26

5175

1205

6.66

5504

1253

7.06

5,838

9,000

1053

5.85

4836

1104

6.23

5155

1154

6.63

5478

1202

7.02

5808

1248

7.43

6142

1294

7.84

6,483

9,500

1106

6.65

5498

1155

7.04

5824

1202

7.44

6155

1248

7.85

6492

1293

8.26

6833

1336

8.68

7,179

10,000

1159

7.52

6214

1206

7.92

6547

1251

8.33

6886

1295

8.74

7229

1338

9.16

7577

1380

9.59

7,929

10,500

1213

8.45

6984

1257

8.86

7325

1300

9.28

7671

1342

9.70

8020

1384

10.13

8375

1424

10.56

8,733

11,000

1266

9.45

7810

1309

9.87

8159

1350

10.29

8511

1391

10.73

8868

1431

11.16

9229

1470

11.60

9,594

11,250

1293

9.97

8245

1334

10.40

8597

1375

10.83

8953

1415

11.26

9313

1454

11.70

9677

1493

12.15

10,045

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.4

1.6

1.8

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

7,000

1189

5.47

4,524

1239

5.87

4,854

1288

4.91

5191

7,500

1224

6.08

5,026

1272

6.48

5,362

1320

5.56

5703

8,000

1261

6.75

5,577

1307

7.16

5,917

1353

6.26

6263

8,500

1299

7.47

6,177

1344

7.89

6,523

1388

7.02

6873

9,000

1338

8.26

6,828

1382

8.68

7,179

1424

7.85

7534

9,500

1379

9.11

7,530

1421

9.54

7,887

1462

8.74

8247

10,000

1421 10.02

8,286

1461

10.46

8,648

1501

9.70

9014

10,500

1464 11.00

9,096

1503

11.45

9,464

1541

10.73

9835

11,000

1508 12.05

9,963

1546

12.50

10,336

11,250

1530 12.60

10,417

Bhp

Brake Horsepower

Watts —

Input Watts to Motor

COMPONENT

CFM

5400

6000

7200

9000

10,000

11,250

EconoMi$er

0.06

0.07

0.09

0.11

0.12

0.14

Glycol Coil

0.30

0.35

0.44

0.58

0.66

0.77

Electric Heat (kW)

26/34

0.08

0.09

0.11

0.15

0.17

0.20

32

0.08

0.09

0.11

0.15

0.17

0.20

42/56

0.11

0.12

0.15

0.19

0.21

0.24

55

0.11

0.12

0.15

0.19

0.21

0.24

56/75

0.14

0.15

0.20

0.24

0.26

0.29

80

0.14

0.15

0.20

0.24

0.26

0.29

Perfect Humidity™ Dehumidification
Package

0.06

0.07

0.10

0.16

0.20

0.25

FIOP — Factory-Installed Option

Advertising