Bryant 619FNQ User Manual

Page 4

Advertising
background image

—4—

Table 4A — 619FNF Physical Data

LEGEND

*See Table 3 for factory charge and additional field charge requirements.

SYSTEM SIZE

018

024

030

036

NOMINAL CAPACITY (Btuh)

17,000

23,600

29,000

36,400

OPERATING WEIGHT (lb)

49

91

95

95

SEER

13

REFRIGERANT*

R-410A

Control (Cooling)

AccuRator Control

INDOOR FAN

Direct Drive Centrifugal

Rpm/Cfm High

1000/470

440/690

660/910

660/910

Rpm/Cfm Medium

890/420

360/560

550/760

550/760

Rpm/Cfm Low

730/340

300/470

470/670

470/670

Motor Watts

120

110

210

210

Blowers Quantity...Size (in.)

1...11.1

INDOOR COIL

Copper Tube, Aluminum Fin

Face Area (sq ft)

3.2

4.8

4.6

4.6

No. of Rows

2

2

3

3

Fins/in.

22

18

18

18

Circuits

5

6

10

10

FILTERS

Cleanable

Quantity...Size (in.)

1...17 x 16

AIRSWEEP

Horizontal

Auto/Preset

OPERATING LIMITS

Cooling (Min/Max)

55 F/125 F

CONTROLS

Integrated Microprocessor

Remote Controller Options

Wireless, CRC

Diagnostics

Yes

Defrost Method

Demand Defrost

Timer Mode

Yes

Warm Start Feature

Yes

Test Mode

Yes

Freeze Protection

Yes

Dehumidification Mode

Yes

Fan Mode

High/Medium/Low/Auto

Auto Changeover

Yes

Auto Restart

Yes

Control Voltage

24

System Voltage

208/230

REFRIGERANT LINES

Connection Type

Flare

Flare

Flare

Flare

Mixed-Phase Line (in.) OD

3

/

8

3

/

8

3

/

8

3

/

8

Vapor Line (in.) OD

5

/

8

5

/

8

3

/

4

3

/

4

Max Length (ft)

200

200

200

200

Max Lift (Fan Coil Above) (ft)

60

60

60

60

Max Lift (Fan Coil Below) (ft)

60

60

60

60

CONDENSATE DRAIN SIZE (in.)

1

1

1

1

CRC

Carrier Room Controller

SEER — Seasonal Energy Efficiency Ratio

Advertising