III. STEP 3 — LOCATING AND MOUNTING THE ROOM
CONTROLLER

A. Locating the Room Controller
See Fig. 14 for room controller dimensions. If the air sensor

in the room controller is going to be used, the room controller

should be located by considering the following:
• Position controller with a minimum clearance of 5 ft from

the floor.

• Locate the unit in the same area as the fan coil unit; pref-

erably on an inside partitioning wall.

• Locate on a section of the wall without pipes or ductwork.

Do not locate close to a window, on an outside wall, or

next to a door leading to the outside.

Do not locate where the controller is exposed to direct

light and heat from a lamp, sun, fireplace, or other tem-

perature-radiating object that may cause a false reading.

Do not locate close to, or in direct airflow of, a heating or

cooling supply.

Do not locate in areas with poor circulation, such as

behind a door or in an alcove.

NOTE:

Do not exceed 500 ft of network wiring when mount-

ing the room controller.

WARNING:

Electrical shock can cause personal

injury and death. Shut off all power to this equipment

during installation. There may be more than one dis-

connect switch. Tag all disconnect locations to alert

others not to restore power until work is completed.

Frame support brackets

Power connection
cables from frame

Power connection
cables from unit

Safety cord
Cable clamp

Frame support
screws

7-7/8”(200 mm)

2%

2” (50 mm)

max.

Fig. 10 — Condensate Drain Pipe

Fig. 11 — Attach Frame Assembly

Fig. 12 — Fix Frame in Position

A AIR B

A. Gasket "A"
B. Gasket "B"

Fig. 13 — Gasket Location