MAXIMUM ALLOWABLE PIPE LENGTH (FT) (CONTINUED)

ALTITUDE (FT)

UNIT MAX

INPUT RATE

(BTUH)

DIRECT VENT (2-PIPE) ONLY

NON-DIRECT VENT

(1-PIPE) ONLY

NUMBER OF 90° ELBOWS

TERMINATION

TYPE

PIPE DIA

(IN.)*

PIPE DIA

(IN.)*

1

2

3

4

5

6

4001 to 5000‡

60,000

2 Pipe or 2-in

Concentric

1-1/2

1-1/2

15

10

5

NA

NA

NA

2

2

64

59

58

53

52

52

80,000

2 Pipe or 2-in

Concentric

2

2

44

39

26

21

20

11

2-1/2

2-1/2

70

70

70

70

70

70

100,000

2 Pipe or 3-in

Concentric

2-1/2

2-1/2

31

22

13

12

NA

NA

3

3

70

70

67

62

57

52

120,000

2 Pipe or 3-in.

Concentric

3† no disk

NA

53

46

40

33

26

20

NA

3†

56

55

54

53

52

52

4† no disk

4† no disk

70

70

70

70

70

70

ALTITUDE (FT)

UNIT MAX

INPUT RATE

(BTUH)

DIRECT VENT (2-PIPE) ONLY

NON-DIRECT VENT

(1-PIPE) ONLY

NUMBER OF 90° ELBOWS

TERMINATION

TYPE

PIPE DIA

(IN.)*

PIPE DIA

(IN.)*

1

2

3

4

5

6

5001 to 6000‡

60,000

2 Pipe or 2-in

Concentric

1-1/2

1-1/2

14

9

NA

NA

NA

NA

2

2

60

55

54

49

48

47

80,000

2 Pipe or 2-in

Concentric

2

2

41

36

23

18

17

8

2-1/2

2-1/2

70

70

70

70

70

70

100,000

2 Pipe or 3-in

Concentric

2-1/2

2-1/2

29

21

12

11

NA

NA

3

3

70

67

62

57

52

47

120,000

2 Pipe or 3-in.

Concentric

3† no disk

NA

42

35

29

22

15

9

NA

3†

53

52

50

49

48

47

4† no disk

4† no disk

70

70

70

70

70

70

ALTITUDE (FT)

UNIT MAX

INPUT RATE

(BTUH)

DIRECT VENT (2-PIPE) ONLY

NON-DIRECT VENT

(1-PIPE) ONLY

NUMBER OF 90° ELBOWS

TERMINATION

TYPE

PIPE DIA

(IN)*

PIPE DIA

(IN)*

1

2

3

4

5

6

6001 to 7000‡

60,000

2 Pipe or 2-in

Concentric

1-1/2

1-1/2

13

8

NA

NA

NA

NA

2

2

57

52

50

45

44

43

80,000

2 Pipe or 2-in

Concentric

2

2

38

33

21

16

15

6

2-1/2

2-1/2

70

70

68

67

66

64

100,000

2 Pipe or 3-in

Concentric

2-1/2

2-1/2

27

19

10

9

NA

NA

3

3

68

63

58

53

48

43

120,000

2 Pipe or 3-in.

Concentric

3† no disk

NA

31

24

18

11

NA

NA

NA

3†

49

48

47

45

44

43

4† no disk

4† no disk

70

70

70

70

67

62

See notes at end of table

COMBUSTION-AIR AND VENT PIPING FOR DIRECT VENT (2-PIPE)

AND NON-DIRECT VENT (1-PIPE) APPLICATIONS continued

Advertising