Bryant 4-WAY MULTIPOISE TWO-STAGE CONDENSING GAS FURNACE 352AAV User Manual

Page 8

Advertising
background image

—8—

352AAV

COMBUSTION-AIR AND VENT PIPING FOR DIRECT VENT (2-PIPE)

AND NON-DIRECT VENT (1-PIPE) APPLICATIONS continued

MAXIMUM ALLOWABLE PIPE LENGTH (FT) (CONTINUED)

ALTITUDE (FT)

UNIT SIZE

(BTUH)

DIRECT VENT (2-PIPE) ONLY

NON-DIRECT VENT

(1-PIPE) ONLY

NUMBER OF 90° ELBOWS

TERMINATION

TYPE

PIPE DIA

(IN.)*

PIPE DIA

(IN.)*

1

2

3

4

5

6

7001 to 8000‡

60,000

2 Pipe or 2-in

Concentric

1-1/2

1-1/2

12

7

NA

NA

NA

NA

2

2

53

48

46

41

40

38

80,000

2 Pipe or 2-in

Concentric

2

2

36

31

19

14

12

NA

2-1/2

2-1/2

66

65

63

62

60

59

100,000

2 Pipe or 3-in

Concentric

2-1/2

2-1/2

25

17

8

7

NA

NA

3

3

63

58

53

48

43

38

120,000

2 Pipe or 3-in.

Concentric

3† no disk

NA

20

13

7

NA

NA

NA

NA

3†

46

44

43

41

40

38

4† no disk

4† no disk

61

56

51

46

41

36

ALTITUDE (FT)

UNIT SIZE

(BTUH)

DIRECT VENT (2-PIPE) ONLY

NON-DIRECT VENT

(1-PIPE) ONLY

NUMBER OF 90° ELBOWS

TERMINATION

TYPE

PIPE DIA

(IN.)*

PIPE DIA

(IN.)*

1

2

3

4

5

6

8001 to 9000‡

60,000

2 Pipe or 2-in

Concentric

1-1/2

1-1/2

11

6

NA

NA

NA

NA

2

2

49

44

42

37

35

34

80,000

2 Pipe or 2-in

Concentric

2

2

33

28

17

12

10

NA

2-1/2

2-1/2

62

60

58

56

55

53

100,000

2 Pipe or 3-in

Concentric

2-1/2

2-1/2

23

15

7

5

NA

NA

3

3

59

54

49

44

39

34

120,000

2 Pipe or 3-in.

Concentric

3† no disk

NA

10

NA

NA

NA

NA

NA

NA

3†

43

41

39

37

35

34

4† no disk

4† no disk

35

30

25

20

15

10

ALTITUDE (FT)

UNIT SIZE

(BTUH)

DIRECT VENT (2-PIPE) ONLY

NON-DIRECT VENT

(1-PIPE) ONLY

NUMBER OF 90° ELBOWS

TERMINATION

TYPE

PIPE DIA

(IN.)*

PIPE DIA

(IN.)*

1

2

3

4

5

6

9001 to 10,000‡

60,000

2 Pipe or 2-in

Concentric

2

2

45

40

38

33

31

29

80,000

2 Pipe or 2-in

Concentric

2

2

30

25

14

9

7

NA

2-1/2

2-1/2

57

55

53

51

49

47

100,000

2 Pipe or 3-in

Concentric

2-1/2

2-1/2

21

13

5

NA

NA

NA

3

3

54

49

44

39

34

29

120,000

2 Pipe or 3-in.

Concentric

NA

3†

39

37

35

33

31

29

4† no disk

4† no disk

10

5

NA

NA

NA

NA

*Disk usage-Unless otherwise specified, use perforated disk assembly (factory-supplied in loose parts bag). If one disk is stated, separate 2 halves of perforated disk
assembly and use shouldered disk half. When using shouldered disk half, install screen side toward inlet box.
†Wide radius elbow.
‡Vent sizing for Canadian installations over 4500 ft (1370 m) above sea level are subject to acceptance by the local authorities having jurisdiction.
NA-Not Allowed; pressure switch will not make.

NOTES:

1. Do not use pipe size greater than those specified in table or incomplete combustion, flame disturbance, or flame sense lockout may occur.
2. Size both the combustion-air and vent pipe independently, then use the larger diameter for both pipes.
3. Assume two 45° elbows equal one 90° elbow. Wide radius elbows are desirable and may be required in some cases.
4. Elbows and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
5. The minimum pipe length is 5 ft for all applications.
6. Use 3-in. diameter vent termination kit for installations requiring 4-in diameter pipe.