HOSE FRICTION LOSS (PSI PER 100 FEET)

GPM Flowing

¾” Booster

1” Booster

1 1/2” Hose

GPM Flowing

1 ¾” Hose with

1 1/2” Couplings

2” Hose with

1 1/2” couplings

2 1/2” Hos

e

3" Hose with

2 1/2" Couplings

3" Hose

GPM Flowing

3 1/2" Hose

4" Hose

5" Hose

10

13.5

3.5

95

14

8

500

9.5

3

20

44

6

125

24

13

750

20

11

5

30

99

14

150

35

18

1000

34

20

8

40

176

24

4

175

47

25

6

1250

53

31

13

50

38

7

200

62

32

8

1500

74

45

18

60

54

9

225

10

1750

61

25

70

12

250

13

5

4

2000

32

80

15

275

15

95

22

300

18

125

38

325

22

8

150

54

350

25

8

500

20

17

750

45

38

1000

80

68


NOTE: Add 5 PSI for each story of building and each wye or siamese. Friction Loss
Calculations courtesy of IFSTA.