Installation (cont’d)

Support and Mounting

Mount the generator on a concrete slab capable of supporting the weight of

the generator. The slab must extend on all sides beyond the frame by at

least one foot. Contact a cement contractor for slab specifications if

necessary. Attach the frame to the concrete slab using 3/8” diameter

expansion anchor bolts (not supplied).

Grounding

Connect a #6 AWG grounding wire (not included) from the ground

connector on the generator to a grounding rod (not included) that has

been driven at least 24 inches deep into the earth. The grounding rod must

be an earth-driven copper or brass rod (electrode) which can adequately

ground the generator.

Note: It is recommended that only a trained and licensed
electrician perform this procedure.