Individual Control Heaters

The bypass orifice is located in the valve body of the

individual controlled heaters. Its purpose is to supply low

pressure gas to the inner combustion cone when heat

demand is satisfied.

The orifice may become plugged with dirt after significant

heater use. Symptoms of a plugged orifice are:

-- Inner cone goes out when thermostatic head cycles

heater back to low heat.

-- Flame back flashing through air intake at injector

body.

Refer to the following instructions:

1. Apply wrenches to the flats of the valve body and the

adapter nut. See Fig. 13.

2. Loosen the adapter nut at the outlet of the valve

body.

3. Pull the control assembly with adapter and adapter

nut from the valve body. See Fig. 13.

4. Using a 3/16 in. nut driver, remove the orifice from

valve body. See Fig. 14. Clean or replace if

necessary. At reinstallation, do not overtighten as

thread damage may occur.

FIG. 13

FIG. 14

1155

LOW FIRE ORIFICE

THERMOSTATIC
HEAD

BYPASS ORIFICE

THERMOSTATIC

HEAD

SAFETY GAS CONTROL VALVE

1. Disconnect the gas hose.

2. Loosen the gas supply tube compression nut and

swing the tube away from the safety control valve.

3. Remove the thermocouple from the safety control

valve.

4. Loosen the screw on the injector body.

5. Remove the safety gas control valve with injector tube

from the heater.

6. Remove the injector tube.

FIG. 12

PILOT SAFETY VALVE

SCREW

BYPASS GAS SUPPLY TUBE

THERMOCOUPLE

INJECTOR BODY

INJECTOR TUBE

SAFETY CONTROL VALVE

GAS SUPPLY TUBE