AEM 30-3020M Water Methanol Failsafe Device User Manual

Page 5

Advertising
background image

Page 5



Alarm Configuration

Option

Description

Aux Input Status

Shows the status of the auxiliary alarm input; on or off

Alarm Delay

Period of time that measured flow can be outside the upper and low flow limit lines before an
alarm condition is triggered; 100-1000 milliseconds

Alarm Reset

Period of time flow must be within the acceptable range before the alarm will automatically reset;
1-10 seconds

Disable Auto Reset

Select to require power cycle to reset alarm; overrides the automatic alarm reset period. NOTE:
this option is only applicable to software version 1.3.0.0

12V Output

Select to turn the 12V output on when an alarm is triggered or to turn the 12V output off when an
alarm is triggered; 1.5 amps max

GND Output

Select to turn the ground output on when an alarm is triggered or to turn the ground output off
when an alarm is triggered; 1.5 amps max

Alarm Status

Parameter

Description

Status Indicator

Color indicates status; green is system ready, red is alarm triggered

Source

Indicates the source of the alarm condition; possible alarm conditions are high flow, low flow,
auxiliary input, and alarm test

Alarm Flow

Flow rate when alarm was triggered; cc/min

Alarm INJ

Injection percentage when alarm was triggered

Option

Description

Alarm Test

Simulates an alarm to test output configuration; test duration set by Alarm Delay value