Receiving & Installation 3-3

MN2412

Electrical Connections Continued

Table 3-1 Single Phase Power Receptacle Description

Model

Electrical Connection Information (Receptacle Provided at Panel)

Straight 120VAC

(20Amp)

Twist Lock 120VAC

(30Amp)

Twist Lock 120/240VAC

(30Amp)

Rated Watts/

(Full load Amps

120/240)

PC30H

3- 15AMP 120VAC

3000 / (22.5/-)

PC40H

2- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

4000 / (33.3/16.7)

PC50H

2- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

5000 / (33.3/16.7)

PC60H

2- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

6000 / (45.8/22.9)

PC90VE

2- 5-20R GFCI 120VAC

1- L5-30R 120VAC

1- L14-30R 120/240VAC

9000 / (66.7/33.4)

Note: GFCI is Ground Fault Protected power.

Class 1 wiring methods must be used for field wiring connections to terminals of a Class 2 circuit.

Figure 3-2 Receptacle Connections

X

(GOLD)

G

W

(SILVER)

NEMA

L5-30R

125V

30A

(GOLD)

X

G

W

(SILVER)

Y

(GOLD)

NEMA

L14-30R

125/250V

30A

NEMA 5-20R

125V 20A

Frame Ground Connection
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power

before you ensure that grounds are connected. Electrical shock can cause serious or fatal

injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be

connected to an approved earth ground. Local codes may also require proper grounding of

generator systems.

The NEC requires that the frame and exposed metal surfaces be at local ground reference

potential to avoid electrical shock hazard. A local ground reference may require a driven earth

ground conductor at the generator installation site. Make the ground connection as shown in

Figure 3-3. Use the appropriate size wire (normally 6 AWG) as required by NEC and local

codes. The local reference ground is normally a copper clad earth ground rod driven into the

earth at least 8 feet.

WARNING: Do not connect the generator output neutral to the frame or local ground. The generator

output is isolated from ground. NEC and local codes require that the generator output remain

isolated from local ground reference.