Appendix A

Powerchief

R Series

Powerchief

R Series A-1

MN2412

Information in this Appendix applies to the following Baldor Generators:

PC30H, PC40H, PC50H, PC60H, PC90VE

Caution:

The brass connecting tab on some 120VAC duplex receptacles have been removed. Each

receptacle is powered by a separate generator winding. When replacing a receptacle, inspect

the brass tab that normally links both receptacles. If it is removed, be sure to remove the

brass tab from the replacement receptacle before it is installed. Failure to remove the tab will

cause a direct short to the generator windings and cause possible generator damage.

Operator Panel Configuration

Figure A-1 PC30H Operator Panel

Duplex Receptacle.

Duplex receptacle is rated at 125VAC, 15 Amps.
Receptacle. Single style receptacle rated for 125VAC, 15 Amps.
Circuit Breaker.

Provide overload protection for the generator set.

Press to Reset

Figure A-2 PC40H, PC50H, PC60H, PC90VE Operator Panel

NEMA 5-20R GFCI Receptacle.

This ground fault circuit interrupter duplex receptacle is rated at 125VAC, 20 Amps.
NEMA L5-30R Receptacle. Twist-lock style receptacle rated for 125VAC, 30 Amps.
NEMA L14-30R Receptacle. Twist-lock style receptacle rated for 125/250VAC, 30 Am
Circuit Breakers.

Provide overload protection for the generator set.

120 VOLTS

120 VOLTS

CIRCUIT BREAKERS

120/240 VOLTS

Press to Reset