4 operation – Baldor MN2412 User Manual

Page 19

Advertising
background image

Section 4

Operation

Operation 4-1

MN2412

Operator Control Panel

Each operator panel is slightly different, depending on features of the generator you purchased.

The Operator Control Panel of Figure 4-1 is shown because it has most of the available features.

This will be used to explain how the controls operate.

Figure 4-1 Operator Control Panels

Press to Reset

120 VOLTS

120 VOLTS

CIRCUIT BREAKERS

120/240 VOLTS

Press to Reset

AC Circuit Breakers

Provide overcurrent protection for the generator output. When tripped, the plunger (in

center of breaker) will extend out about 3/8 inch. Remove the loads, push the plunger

into the breaker to reset the breaker the restore the loads.

WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician

has installed an approved transfer switch. The National Electrical Code (NEC) requires that

connection of a generator to any elastical circuit normally powered by means of an electric

utility must be connected by means of approved transfer switch equipment so as to isolate

the electrical circuit from the utility distribution system when the generator is operating.

Failure to isolate the electrical circuits by such means may result in injury or death to utility

power workers due to backfeed of electrical energy onto the utility lines.

Receptacles – Receptacles are provided to allow easy connection of electrical loads. Never connect this

generator to any buildings electrical system unless a licensed electrician has installed an

approved transfer switch. Multiple receptacles may be used at the same time provided the total

electrical load does not exceed the generators rated output.

120Volts –

PC30H has no GFCI protection, 3 outlets rated 125VAC at 15 Amperes.

All others have NEMA 5–20R GFCI Duplex receptacle provides ground fault

protection. Rated 125VAC at 20 Amperes.

30 Amps 120 Volts –

Twist lock NEMA L5–30R receptacle, rated 125 Volts at 30 Amperes.

30 Amps 120/240 Volts – Twist lock NEMA L14–30R receptacle rated 250Volts at 30 Amperes.

Note: The nominal voltage produced by the generator at each receptacle is 120VAC or 240VAC.

Advertising