VENTILATION EVALUATION

UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced unit

efficiency, capacity or unit life.
DO NOT use HRV during construction of a house or when

sanding drywall. This type of dust may damage system.

CAUTION

!

Ventilator Sizing

Tables 3 and 4 should be used to determine the required airflow for

a home. These guidelines are taken from ASHRAE 62.2--2004.

Table 3 – Ventilation Air Requirements, cfm

FLOOR

AREA (ft

2

)

BEDROOMS

0---1

2---3

4---5

6---7

>7

<1500

30

45

60

75

90

1501---3000

45

60

75

90

105

3001---4500

60

75

90

105

120

4501---6000

75

90

105

120

135

6001---7500

90

105

120

135

150

>7500

105

120

135

150

165

Table 4 – Ventilation Air Requirements, L/s

FLOOR

AREA (m

2

)

BEDROOMS

0---1

2---3

4---5

6---7

>7

<139

14

21

28

35

42

139.1---279

21

28

35

42

50

279.1---418

28

35

42

50

57

418.1---557

35

42

50

57

64

557.1---697

42

50

57

64

71

>697

50

57

64

71

78

CONTROL BOARD OPERATION

Defrost

The ERV/HRV continually monitors the outside air temperature. If

the outside air is at or below 23°F (--5°C), the ERV/HRV will

initiate a defrost cycle by closing the outside air damper and

recirculating warm indoor air through the heat recovery core. This
happens every 32 minutes with a 6 minute defrost cycle. During

this process, core is defrosted without the use of electric strip heat.

At 5°F (--15°C), unit will defrost for 6 minutes every 32 minutes.

At --17°F (--27°C), the unit will sense a need to defrost every 20

minutes with a 6 minute cycle. See the Troubleshooting section for
a control logic explanation.

Off and Intermittent/Off Mode

When ERV/HRV is Off, K1 relay is open, and K5 relay is

energized which closes outside air damper.

High--Speed Air Exchange

When high--speed air exchange occurs, K1 and K2 relays are

energized and K5 relay is de--energized. This opens low--speed
contacts, and closes high--speed contact on K2 relay. This also

opens contact on K5 relay which opens outside air damper. Then,

115VAC is applied between orange and gray wires on Molex plug
(pins 1 and 6) and blower motor runs in high--speed operation.

Low--Speed Air Exchange

When low--speed air exchange occurs, K1 Relay is energized
which closes the contacts. K2 and K5 relays are de--energized. This

keeps low--speed contacts closed and high--speed contacts open on

K2 relay, and opens outdoor air damper. 120VAC is applied

between Red and Gray wires on Molex plug (pins 1 and 4) and
blower motor runs in low--speed operation.

CARE AND MAINTENANCE

Door

ERV/HRV door can be removed by unlatching brief case style
latches, then slide door to the right and remove it from hinges.

Door must be in place and secured shut for proper operation.

Filter

Filters in ERV/HRV are washable and should be cleaned every 3
months. Use a vacuum cleaner to remove heaviest portion of

accumulated dust, then wash in lukewarm water. Allow filter to
completely dry before reinstalling. A dirty air filter will cause

excessive strain on blower motor. Never operate unit without a

filter. Vacuum out debris.
In addition, regularly check and clean screens on exterior intake

and exhaust hoods when necessary.

UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in unit component

damage.
DO NOT clean filters in a dishwasher and DO NOT dry

them with a heating appliance or permanent damage will

result.

CAUTION

!

Blower Motor and Wheel

ERV/HRV blower motors are factory lubricated for life.

Lubricating bearings is not recommended. However, inspect and
clean any accumulated dirt and grease from blower motor and

wheel annually.

Cleaning the Core

ERV is equipped with a special energy recovery core which utilizes

a special membrane and allows transfer of sensible and latent

energy. The core should always be vacuumed only every 3 months
to remove dust and dirt that could prevent transfer of energy. (See

Fig. 15 and 16.)