Model 99FRD, 100CRD & 102CRD oil burners — Instruction manual

Carlin part number MN99102 Rev. 10/21/10

– 14 –

Wire burner — 48245 primary control

1. All wiring must comply with:

• In the U.S — the National Electrical Code, ANSI Z223.1/NFPA 54.
• In Canada — the Canadian Electrical Code Part 1, CSA standard C22.1.
• All applicable local codes/standards.

2. Wire the burner following Figure 16 and any special instructions or wiring

diagram provided with the appliance, burner or other components.

3. The burner requires a 120 VAC/60 hz/single-phase power supply, with at least

a 5-amp fuse. The current draw (equipped with Carlin PSC motor) will be ap-
proximately 2.5 amps.

4. The 48245 thermostat terminals provide a power source. Never apply external

power to these terminals under any circumstances. To avoid this problem when
using zone valves, disconnect fi eld wires from 48245 thermostat terminals.
Then connect a voltmeter across wires. Operate all zones and verify that there
is never a voltage reading at the meter. A voltage reading indicates incorrect
wiring that must be corrected before attempting to operate the burner.

5. Make sure the burner and appliance are correctly wired and the line switch is

properly fused for the load.

To start burner

Do not start the burner if the combustion chamber contains

oil or oil vapor.

1. Turn service switch OFF.

2. Perform inspections and checkouts on pages 14 and 15.

3. Slip one end of a 3/16-inch I.D. clear plastic hose over end of bleed valve, the

other end into a container. Then open bleed valve.

4. Set thermostat (operating controls) to call for heat.

5. Turn service switch ON.

6. Bleed oil line until plastic line is free of bubbles; then another 15 seconds longer.

(Should the primary control timing cause a lockout during purging, restart the
burner following the primary control data sheet instructions.)

7. Close bleed valve. The burner should cycle through the sequence given in the

primary control data sheet.

8. Perform primary control fl ame failure lockout and safety timing tests per instruc-

tions in primary control data sheet.

9. Should control/burner fail to operate correctly, see page 15 for suggestions in

troubleshooting.

Figure 16 Burners up to 3.0 GPH only, wiring using Carlin 48245 primary control (see appliance manual or separate wiring

information for burner equipped with a primary control not covered in this manual)

4. Wire burner • start burner — 48245 primary control

Turn off power to appliance when servicing burner. Failure to comply could result in severe personal injury, death or substantial property damage.