Bryant HUM-56-1 User Manual

Page 10

Advertising
background image

VIII.

INSTALL HUMIDISTAT AND COMPLETE WIRING

1. Mount humidistat on inside wall or return-air duct in

accordance with section INSTALLATION OF HUMIDIS-
TAT on page 10.

NOTE:

Wiring must comply with national electrical code and any

local codes or ordinances that may apply. (See Fig. 17.)

IX.

START-UP

1. Open saddle valve to permit water to flow to the solenoid

valve.

2. Check all connections for water leaks.

3. Set thermostat to call for heat. Set humidistat at highest

humidity setting to be sure the contacts are closed. After a
few minutes of operation, check the drain connection for
leaks and to see if water is flowing through humidifier.

4. Reverse thermostat and humidistat settings to insure proper

shutdown.

5. Reset thermostat to normal setting. Reset humidistat to

recommended setting.

X.

FINAL STEPS

Attach humidifier maintenance instruction sticker to a visible
location.

1. Inform homeowner of proper operation, maintenance, and

humidistat setting.

a. If unit is installed during cooling season, close bypass

damper, set humidistat for summer setting (OFF or
lowest setting).

b. If installed during heating season, set unit for normal

operation.

INSTALLATION OF HUMIDISTAT

The humidistat provides automatic control of humidifiers in
central heating systems. It is designed for low voltage, wall, or
surface duct mounting and contains a SPST snap-acting dustproof
switch.

CAUTION:

Disconnect power supply before making

wiring connections to prevent possible electrical shock
and equipment damage. Make wiring connections in
accordance with Installation Instruction supplied with the
humidifier.

1. Installer must be a trained, experienced service person.

2. Disconnect power supply before beginning installation.

3. Conduct a thorough checkout before leaving installation.

I.

WALL MOUNTING (LOW VOLTAGE)

1. Choose a location for humidistat about 5 ft above floor on

inside wall with average room temperature and relative
humidity conditions. Maximum ambient temperature of
selected location must not exceed 125°F. Humidistat may
be mounted directly on wall.

2. Drill a small hole in wall and run low-voltage wiring to

location chosen. Pull about 6 in. of wire through hole. Plug
opening to prevent drafts from affecting humidistat opera-
tion.

3. Remove knob, faceplate, and switch assembly from case by

following steps listed below.

a. Remove knob by pulling away from casing. (See Fig.

18.)

b.

Lift off faceplate, starting at right side. Left end of

faceplate protrudes under lip of casing. (See Fig. 18.)

c. Remove switch by removing 2 screws in back of casing.

Pressing tab on case. Lift out control. (See Fig. 19.)

4. Make connections to screw terminals on switch assembly.

Re-install switch into casing — secure with 2 short screws.

5. Mount case horizontally over wires directly to wall using 2

long screws provided.

6. Replace faceplate and knob.

Fig. 15—Valve and Media Assembly for HUMBBWTR2019-A--

A98370

PIN

FLOAT

ARM

GASKET

RETAINER

BEARING

VALVE SEAT

SUPPORT
BRACKET

(LEFT HAND INSTALLATION SHOWN)

FLOAT VALVE ASSEMBLY

REINSTALLING MEDIA ASSEMBLY

VALVE BODY

WASHER

1

4

IN.

BLUNT

POINT SCREW

1

2

IN.

LONG

SCREW

Fig.17—Humidistat Installation for HUMBBWTR2019-A--

A96014

MOTOR

HUMIDISTAT

115V

FIELD

WIRING

TRANSFORMER

(10-VA)

24V

MOTOR

HUMIDISTAT

24VAC

FURNACE

—10—