V.

OPERATION

When relative humidity falls to humidistat set point, the humidistat
switch makes contact and starts humidifier. In some central unit
humidifier systems, furnace fan must be operating before humidi-
fier will start. An increase in relative humidity above set point will
stop humidifier.

VI.

CHECKOUT

Place system in operation and observe at least 1 complete cycle to
make certain that all components are functioning properly.

Fig. 21—Humidistat Installation Schematic

A97105

CASE

MOUNTING TEMPLATE

MOUNTING SCREWS (2)

FOAM GASKET

MAKE OPENING IN DUCT

MOUNT HUMIDISTAT CASE

ALTERNATE PROCEDURE:

DRILL SIX 1/4 IN.
DIAMETER HOLES

RECOMMENDED HUMIDISTAT SETTING

OUTSIDE

TEMPERATURES

RECOMMENDED

HUMIDISTAT SETTING

-20°F

15%

-10°F

20% (LO)

0°F

25%

+10°F

30%

+20°F

35%

+30°F

40% (MED)