Det-Tronics PIRECL Infrared Hydrocarbon Gas Detector PointWatch Eclipse SAFETY MANUAL User Manual

Page 2

Advertising
background image

5.1

95-8630

2

DESiGN
The PIRECL is an infrared hydrocarbon gas detector

that is classified as Type B smart device according

to IEC61508. It provides an isolated 4-wire 4-20 mA

output that is proportional to hydrocarbon vapor

concentrations from 0-100% lower flammable limit

(LFL). The PIRECL contains extensive self-diagnostics

and is programmed to send the current output to a

specified failure state (3.6 mA or less) upon internal

detection of a failure. Optional Alarm and Fault relay

contact outputs are available in addition to the analog

signal output, and can be programmed in the field

by the user. The Safety Certification for the PIRECL

includes both the standard version with analog output

only and the version with analog output and optional

relay outputs.

Safety-Certification of the PIRECL includes:
• the High Alarm, Low Alarm, and Fault relay outputs
• the 4-20 mA output.

RS-485 Modbus signal output is not part of the SIL

certification.

Det-Tronics FlexVu

®

UD20 Universal Display Unit has

been evaluated as a loop-powered device approved for

use in-line with a Safety-Certified PIRECL. Failure rates

for the PIRECL when connected to a UD20 are listed in

the Failure Rates table at the end of this manual.

Non-interfering interfaces
Safety-Certification of the PIRECL includes the following

non-interfering interfaces:
• LEDs
• Magnetic switches
• HART Communication

The HART communication protocol is non-interfering

and is to be used for diagnostics within the SIL 2

safety loop in the Safety operation mode. Diagnostics

are defined as read only information. Local HART

communication with the PIRECL via the onboard

intrinsically-safe communication port using a handheld

HART field communicator, or AMS program connected

to the 4-20 mA output, is acceptable. Proper

analog signal loop resistance must be installed as

documented in the instruction manual to enable local

HART communication. The end user must perform

calibration after any configuration changes.

VALiD iNPUT rANGE
PIRECL fault and alarm annunciation is provided on the

4-20 mA signal output loop by signaling to a specific

mA current output level. The user SIF must monitor

the 4-20 mA output for fault and alarm conditions

and take appropriate action according to the specific

requirements of the SIF. The receiving device must be

programmed to indicate a fault condition when current

levels reach under-current of 3.6 mA or less or over-

current of 21 mA or more.

NOTE

The PIRECL analog signal output is not safety-
rated during detector warm-up, configuration
mode, calibration mode, and during signal output
loop testing. Alternative means should be used
at the job site to ensure facility safety during
these activities.

DiAGNoSTiC rESPoNSE TiME
The PIRECL will perform all critical diagnostic functions

within one hour, worst case diagnostic detection time.

CErTiFiCATioN
The PIRECL Safety-Certified version is certified SIL 2

Capable by exida

®

to IEC61508 for single input use in

low demand, SIL 2 Safety Instrumented Systems.

SAFETY-CErTiFiED ProDUCT iDENTiFiCATioN
Safety Certification of all PIRECL models meeting SIL

2 safety standards is clearly identified on the product

label.