Det-Tronics PIRECL Infrared Hydrocarbon Gas Detector PointWatch Eclipse SAFETY MANUAL User Manual

Page 3

Advertising
background image

5.1

95-8630

3

iNSTALLATioN

NOTE

For complete information regarding performance,
installation, operation, maintenance and
specifications of PIRECL, refer to the PIRECL
instruction manual.

No special or additional detector installation

requirements exist above and beyond the standard

installation practices documented in the PIRECL

instruction manual.

Environmental operating specifications for the PIRECL

are applicable as published in the general specifications

section in the PIRECL instruction manual. The device

shall not be exposed to environments that exceed its

specified environmental limits.

The PIRECL operating power distribution system

should be designed and installed so that the terminal

voltage does not drop below 18 Vdc when measured

at any specific location. The external system providing

power to the PIRECL must have over-voltage protection

that ensures supply voltage does not exceed 33 Vdc.

The user shall correctly install all shielding and

grounding for the device and ensure that maximum

cable lengths are not exceeded.

NOTE

All safety functions of the PIRECL are active
within 2 minutes of power-up without any user
action required.

CoMMoN MiSUSE SCENArioS
Refer to the Installation, Startup, and Maintenance

sections of the instruction manual for information on

avoidance and resolution of common misuse scenarios.

No special application restrictions are necessary to

meet the safety certification requirements.

NOTE

If the user suspects that damage or misuse has
occurred to the PIRECL, a full proof test shall be
performed.

GENErAL APPLiCATioN CoNSiDErATioNS

• The user shall understand the effects of and limit the

number of devices that are voted to declare alarm.

• The user shall understand the effects of the Alarm

Level set points and limit the threshold so that desired

SIF hazard detection is achieved.

STArT-UP AND CoMMiSSioNiNG

Commission Personnel
The Safety Certified PIRECL can be commissioned by

any qualified person with knowledge of gas detection

instruments and the configuration device being used.

Refer to the Start-Up and Commissioning section

provided in the PIRECL instruction manual.

relay Configuration requirements
The end user must provide transient and current

limiting on the output contacts of the relays. The

maximum relay contact output must be limited to

2 amperes at 30 Vdc. The load must be a resistive

load. The user must protect against transients by

using standard protection methods such as proper

grounding of shielded wire and separation of relay

load wires from other lines carrying rapidly switched

high current (e.g. large motor power supply lines).

If the 4-20 mA analog output is not being monitored

for fault conditions, the status of the fault relay must be

monitored and appropriate action taken.

The fault relay is configured for normally energized

operation.

Advertising