12

95-8472

3.1

Section III —

System Maintenance

TROUBLESHOOTING

Table 3 is intended to serve as an aid in locating the

cause of a malfunction.

The transmitter is not designed to be repaired in the field.

If a problem should develop, first check for proper wiring,

calibration and sensor sensitivity. If it is determined that

the problem is caused by an electrical malfunction in the

transmitter, the unit must be returned to the factory for

repair.

NOTE

Record all faults on the Fault Record Sheet
supplied at the back of this manual.

ROUTINE MAINTENANCE

The Model 505 Transmitter requires no routine

maintenance, except for periodic checks to ensure

proper calibration. The frequency of these checks

is determined by the requirements of the particular

installation. Calibration gas kits are required for these

checks.

CHECKOUT IN NORMAL MODE
The entire gas detection system should be checked

periodically to ensure that the presence of gas at the

sensor will result in the proper system response.

SENSOR INSPECTION
Since a dirty or plugged sensor filter can adversely affect

the response time of the sensor by restricting the flow of

gas to the sensing element, it should be inspected on a

regular basis. If a dust cover or splash shield is used, it

should also be checked.

SENSOR SENSITIVITY
If sensor response to 50% LFL methane is less than 15

millivolts, the sensor should be replaced. Refer to Table

2, “Calibration Procedure” for information regarding

calibration and sensor sensitivity.

SENSOR REPLACEMENT
De-classify the area prior to replacing the sensor and

secure any output devices connected to the system

to prevent unwanted actuation of this equipment. To

replace the sensor:

1. Verify that no hazardous levels of combustible gas

are present at the sensor, then remove the cover

from the junction box.

2. Unplug the sensor from the circuit board and unscrew

it from the junction box.

3. Coat the threads of the new sensor with silicone free

grease, then screw the sensor into the junction box

and plug it into the circuit board.

4. Allow the sensor output to stabilize under power

(about two hours minimum for best results), then

perform the calibration procedure described in the

“Calibration” section of this manual.

5. For the highest degree of calibration accuracy,

perform a second calibration after 24 hours.

A Recommended Test Form is supplied at the back of

this manual for recording maintenance performed on the

system.