Appendix b, Csa approval – Det-Tronics 505 Combustible Gas Detector Transmitter with Combustible Gas Sensor CGS User Manual

Page 19

Advertising
background image

16

95-8472

3.1

APPENDIX B

CSA APPROVAL

THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE CSA APPROVAL.

MODEL 505 SERIES COMBUSTIBLE GAS TRANSMITTER

• Explosion-proof for Class I, Division 1, Groups B, C, & D Hazardous Locations per CSA C22.2 #30.
• Dust/ignition-proof for Class II, Division 1, Groups E, F, & G, Class III Hazardous Locations per CSA C22.2 #25.

(For use with Sensor Termination Box.)

• Enclosure Rating NEMA/Type 4X per CSA C22.2 #94. (For use with Sensor Termination Box.)
• Operating temperature limits are –40°C to +75°C (–40°F to +167°F).
• Storage temperature limits are –55°C to +85°C (–67°F to +185°F).
• Explosion-proof ambient temperature limits are –55°C to +125°C (–67°F to +257°F).
• Relative humidity range is 5 to 95% RH.
• Performance verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152. Accuracy: ±3% LFL

from 0 to 50% LFL, ±5% LFL from 51% to 100% LFL.

• For use with 226365-118 through 226365-125 Sensor Termination Boxes.
• For use with Model CGS Series Combustible Gas Sensor.

NOTE

The high temperature characteristic has not been CSA verified above 75°C.

NOTE

Detector Electronics combustible gas detection K factors are not CSA verified.

NOTE

Metric straight thread types are for use in non-North American applications.

Calibration
• Calibration of the above listed sensors has been CSA verified using the Det-Tronics 225130-001 (50% LFL

methane) Calibration Kit.

Advertising