20

95-8472

3.1

The CGS Combustible Gas Sensor must only be mounted into the enclosures of the Infiniti Gas Transmitter Model

U9500A Series, the Combustible Gas Transmitter Model 505 Series, the Digital Communication Unit EQ 22xxDCUEX

Series or the Sensor Termination Box Model STB Series.

The actual enclosure must provide a maximum measured reference pressure of 15 bar measured according to

IEC 60079-1: 2007, §15.

The CGS Combustible Gas Sensor is to be installed in places where there is a low risk of mechanical damage.

SENSOR TERMINATION BOX (STB)

IECEx ULD 10.0007

Ex d IIC T4–T6 Gb

T6 (Tamb = –55°C to +60°C).

T5 (Tamb = –55°C to +75°C).

T4 (Tamb = –55°C to +125°C).

IP66.

IEC Standards:

IEC 60079-0: 2007

IEC

60079-1:

2007

IEC 60529, 2.1.ed.+Corr. 1:2003+2:2007.