9

95-8493

APPENDIX B

INTRINSICALL

Y

SAFE

CLASS B, STYLE B WIRING

Hazardous (Classified) Locations:

Class I, Division 1, Group C, D

Class I, Division 2, Group

A, B, C, D

Class II, Division 1, Group E, F

, G

Class II, Division 2, Group F

, G

Class III, Division 2

PM-5MP

OR

PM-5MP+

V+

V+

POWER RETURN

POWER RETURN

TROUBLE +

TROUBLE –

ALARM +

ALARM –

ALARM –

ALARM +

END OF LINE DEVICE

HAZARDOUS LOCATIONS:

CLASS I, DIV. 1, GP. C, D

CLASS II, DIV. 1, GP. E, F, G

CLASS III, DIV. 2

NON-HAZARDOUS LOCATION

SAFETY BARRIER

SAFETY BARRIER

CONTROL ROOM

INSTRUMENTATION

OPERATING AT OR

LESS THAN 250

VOLTS RMS.

+24 VDC

DC RETURN

ALARM +

ALARM –

NOTES:

1.

SUIT

ABLE FOR INTRINSICALL

Y

SAFE

INST

ALLA

TION IN CLASS I, DIV

. 1, GP

. C,

D; CLASS I, DIV

. 2, GP

.

A, B, C, D; CLASS

II, DIV

. 1, GP

. E, F & G; CLASS II, DIV

. 2,

GP

. F & G. CLASS III, DIV

. 2 HAZ-

ARDOUS LOCA

TIONS. WIRING METH-

ODS SHALL

BE INST

ALLED IN

ACCOR

DANCE WITH

ANSI/NFP

A

70 (NEC),

ANSI/NFP

A

72 AND

ISA

R

P

12.6.

2.

I. S. BARRIERS MUST

BE INST

ALLED IN

ACCORDANCE WITH

THE

MANUF

ACTURER’S GUIDELINES.

3.

THIS DRA

WING SHOWS ONE SENSOR

CONNECTED IN

A

C

LASS B, STYLE B

CONFIGURA

TION PER NFP

A

72.

MUL

TIPLE SENSORS MA

Y

NOT

BE

CONNECTED

T

O

THE SAME BARRIER.

AN END OF LINE DEVICE (EOL) IS

REQUIRED

T

O

MONIT

OR LINE

CONTINUITY

.

4.

END OF LINE DEVICE V

ALUE PLUS

BARRIER RESIST

ANCE MUST

PROVIDE

ADEQUA

TE SUPER

VISION CURRENT

FOR FIRE

ALARM CONTROL

P

ANEL.

5.

RESIST

ANCE BETWEEN BARRIER

GROUND

AND EAR

TH GROUND MUST

NOT

EXCEED ONE OHM.

6.

PM-5MP

AND PM-5MP+ INTERCON-

NECT

VIA

FL

YING LEAD. EXTENSION

CABLE SHALL

C

OMPL

Y

WITH

ANSI/NFP

A

70 (NEC)

AR

TICLE

504-30(b)(2).

7.

CABLE SHIELD MUST

BE

TIED

T

O

INTRINSIC SAFETY

GROUND

A

T

THE

BARRIER.

8.

THE PM-5MP

AND PM-5MP+ SENSORS

HA

VE BEEN SYSTEM

APPROVED WITH

THE FM

APPROVED BARRIERS LISTED

IN THE

BARRIER T

ABLE.

9.

MAXIMUM CABLE LENGTH: 1000 FEET

.

FIRE SENSOR

ELECTRICAL INTERF

A

C

E

Wire Color

Signal

Red

V+, Input P

o

w

e

r

Or

ange

V+, Input P

o

w

er

Blac

k

P

o

w

er Retur

n

Bro

wn

P

o

w

er Retur

n

Y

ello

w

A

lar

m

+

Green

Alar

m +

Blue

Alar

m

Violet

Alar

m

Gr

a

y

T

roub

le +

White

T

roub

le –

BARRIER P

ARAMETERS

MODEL

MANUF

ACTURER

Vt (V)

It (MA)

9002/77-280-094-00

ST

AHL

28.1

87.0

Z978

PEPPERL

+ FUCHS

30.0

93.0

7278ac

MTL

28.0

94.0

BARRIER T

ABLE

Figure B1—Intrinsically Safe Class B, Style B Wiring (Drawing No. 420032)