Appendix c, Pm-5mp+ pm-5mp, Pm-5mp – Det-Tronics PM-5MP & PM-5MP+ Dual Spectrum IR Flame Detector User Manual

Page 12

Advertising
background image

10

APPENDIX C

NONINCENDIVE

CLASS B, STYLE B WIRING

Hazardous (Classified) Locations:

Class I, Division 2, Group

A, B, C, D

Class II, Division 2, Group F

, G

Class III, Division 2

Non-hazardous (Non-classified) Locations

Figure C1—Non-Incendive Class B, Style B Wiring (Drawing No. 420033)

PM-5MP

OR

PM-5MP+

PM-5MP

OR

PM-5MP+

PM-5MP

OR

PM-5MP+

V+ (RED)

V+ (ORG)

PWR RTN (BLK)

PWR RTN (BRN)

ALARM + (YEL)

ALARM + (GRN)

ALARM – (BLU)

ALARM – (VIO)

TROUBLE + (GRY)

TROUBLE – (WHT)

V+ (RED)

V+ (ORG)

PWR RTN (BLK)

PWR RTN (BRN)

ALARM + (YEL)

ALARM + (GRN)

ALARM – (BLU)

ALARM – (VIO)

TROUBLE + (GRY)

TROUBLE – (WHT)

V+ (RED)

V+ (ORG)

PWR RTN (BLK)

PWR RTN (BRN)

ALARM + (YEL)

ALARM + (GRN)

ALARM – (BLU)

ALARM – (VIO)

TROUBLE + (GRY)

TROUBLE – (WHT)

END OF LINE

DEVICE

CONTROL ROOM

INSTRUMENTATION

+24 VDC

DC RETURN

ALARM +

ALARM –

HAZARDOUS LOCA

TION:

CLASS I, DIV

. 2, GR

OUPS A, B

, C & D

.

CLASS II, DIV

. 2, GR

OUPS F & G.

CLASS III, DIV

. 1 & 2.

NON-HAZARDOUS LOCA

TION

FIRE SENSOR

ELECTRICAL INTERF

A

C

E

Wire Color

Signal

Red

V+, Input P

o

w

e

r

Or

ange

V+, Input P

o

w

e

r

Blac

k

P

o

w

er Retur

n

Bro

wn

P

o

w

e

r Retur

n

Y

ello

w

A

lar

m +

Green

Alar

m +

Blue

Alar

m –

Violet

Alar

m –

Gr

a

y

T

roub

le +

White

T

roub

le –

NOTES:

1.

FOR INST

ALLA

TION IN NONINCENDIVE,

CLASS I, DIVISION 2, GROUPS

A, B, C &

D; CLASS II, DIVISION 2, GROUPS F & G;

CLASS III, DIVISION 2 HAZARDOUS

(CLASSIFIED) LOCA

TIONS, OR NON-

HAZARDOUS LOCA

TIONS ONL

Y

. WIRING

METHODS SHALL

BE INST

ALLED IN

ACCORDANCE WITH

ANSI/NFP

A

70 (NEC)

AR

TICLE 501-4(b)

AND

ANSI/NFP

A

72.

2.

THIS DRA

WING SHOWS

THREE

SENSORS CONNECTED IN ONE ZONE

IN

A

C

LASS B, STYLE B

CONFIGURA

TION PER NFP

A

7

2.

ADDITIONAL

SENSORS CAN BE

ADDED

BY

REPEA

TING

THE WIRING P

A

TTERN

OF THE

CENTRAL

SENSOR.

3.

PM-5MP

AND PM-5MP+ INTERCONNECT

VIA

FL

YING LEAD.

4.

ELECTRICAL

REQUIREMENT

: 9

T

O

30

VDC

AND 10 MILLIAMPS (MAX) PER

SENSOR.

5.

AN END OF LINE DEVICE,

AS

REQUIRED BY

THE FIRE

ALARM

CONTROL

P

ANEL, IS USED

T

O

MONIT

OR LINE CONTINUITY

.